2007-10-17 11:50:38****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)ENGINEER HAS DESIGNED TO ASCE7-05; CORRECT VERSION
 IS ASCE7-02 PER FBC CHAPTER 35.
  
 2.)THE ASSEMBLY THE ENGINEER HAS SPECIFIED, ON PAGES
 27-28 OF THE NOA WITH DP OF -45, REFERS TO GENERAL
 LIMITATION #9.NO ENHANCED FASTENING IS ALLOWED;
 PLEASE SEE NOA.
  
 3.)ALL SHEETS ARE TO BE IN COMPLIANCE WITH
 FAC61G15-23.002.ALL TITLE BLOCK INFORMATION,
 SIGNATURE, SEAL, AND DATE IS TO BE ON EACH SHEET OR AN
 INDEX SHEET IN COMPLIANCE WITH FAC61G15 IS TO BE USED.
  
 4.)ENGINEER HAS SPECIFIED THE SAME PRESSURES FOR ZONE
 3 AS ZONE 2.IF THERE IS A PARAPET WALL AROUND THE
 ENTIRE PERIMETER, PLEASE STATE THIS AS WELL AS HEIGHT
 OF THE PARAPET WALL.
  
 5.)THE ENGINEER MAKES REFERENCE TO A LOSS PREVENTION
 SHEET.ENHANCED FASTENING IS TO BE DONE IN ACCORDANCE
 WITH THE PRODUCT APPROVAL AND RAS117.IT IS NOT CLEAR
 HOW INCREASING FASTENER DENSITY BY 50% FOR ZONE 2 AND
 100% FOR ZONE 3 IS COMPLIANT.A PRESSURE OF -45
 INCREASED 50% GIVES A RESULT OF 67.5, BUT YOU'VE
 DECLARED ZONE 2 PRESSURE AS 71.1.WHY WOULD FASTENERS
 BE DOUBLED, TO MEET A PRESSURE OF -90, WHEN YOU'VE
 DECLARED DESIGN PRESSURE OF -71.1 IN ZONE 3?
  
 6.)NOTE THAT THE FASTENER PATTERN HAS NOT BEEN
 REVIEWED AS ENHANCED FASTENING IS NOT ALLOWED FOR THE
 ASSEMBLY SELECTED.
  
 7.)A SET HAS BEEN RETAINED. WHEN RESUBMITTING, PLEASE
 PROVIDE TWO COMPLETE COLLATED SETS.
  
  
  
  