| 2007-10-17 11:50:38 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | 1.)ENGINEER HAS DESIGNED TO ASCE7-05; CORRECT VERSION |
| | IS ASCE7-02 PER FBC CHAPTER 35. |
| | |
| | 2.)THE ASSEMBLY THE ENGINEER HAS SPECIFIED, ON PAGES |
| | 27-28 OF THE NOA WITH DP OF -45, REFERS TO GENERAL |
| | LIMITATION #9.NO ENHANCED FASTENING IS ALLOWED; |
| | PLEASE SEE NOA. |
| | |
| | 3.)ALL SHEETS ARE TO BE IN COMPLIANCE WITH |
| | FAC61G15-23.002.ALL TITLE BLOCK INFORMATION, |
| | SIGNATURE, SEAL, AND DATE IS TO BE ON EACH SHEET OR AN |
| | INDEX SHEET IN COMPLIANCE WITH FAC61G15 IS TO BE USED. |
| | |
| | 4.)ENGINEER HAS SPECIFIED THE SAME PRESSURES FOR ZONE |
| | 3 AS ZONE 2.IF THERE IS A PARAPET WALL AROUND THE |
| | ENTIRE PERIMETER, PLEASE STATE THIS AS WELL AS HEIGHT |
| | OF THE PARAPET WALL. |
| | |
| | 5.)THE ENGINEER MAKES REFERENCE TO A LOSS PREVENTION |
| | SHEET.ENHANCED FASTENING IS TO BE DONE IN ACCORDANCE |
| | WITH THE PRODUCT APPROVAL AND RAS117.IT IS NOT CLEAR |
| | HOW INCREASING FASTENER DENSITY BY 50% FOR ZONE 2 AND |
| | 100% FOR ZONE 3 IS COMPLIANT.A PRESSURE OF -45 |
| | INCREASED 50% GIVES A RESULT OF 67.5, BUT YOU'VE |
| | DECLARED ZONE 2 PRESSURE AS 71.1.WHY WOULD FASTENERS |
| | BE DOUBLED, TO MEET A PRESSURE OF -90, WHEN YOU'VE |
| | DECLARED DESIGN PRESSURE OF -71.1 IN ZONE 3? |
| | |
| | 6.)NOTE THAT THE FASTENER PATTERN HAS NOT BEEN |
| | REVIEWED AS ENHANCED FASTENING IS NOT ALLOWED FOR THE |
| | ASSEMBLY SELECTED. |
| | |
| | 7.)A SET HAS BEEN RETAINED. WHEN RESUBMITTING, PLEASE |
| | PROVIDE TWO COMPLETE COLLATED SETS. |
| | |
| | |
| | |
| | |