Plan Review Notes
Plan Review Notes For Permit 07100432
Permit Number 07100432
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-25 11:42:30 
  
  
  
 *** DENIED ***
  
 1) NOTE: PLEASE SUBMIT PLANS WHICH STATE THE RELEVANT
 CODES IN DESIGN WHICH ARE CURRENTLY ADOPTED BY THE
 STATE. THE FOLLOWING IS WHAT IS NEEDED FOR ELECTRICAL
 REVIEW.
 2004 FBC W/2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THE VALUE ON THE COMPLETE SCOPE OF
 WORK SHOWN ON PLANS IS REQUIRED TO MEET FBC 108.3. THIS
 VALUE IS TO INCLUDE ALL LABOR, MATERIALS, EQUIPMENT,
 DESIGN COST ETC. (EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED.
 VALUE FOR BUILDING AND ELECTRICAL IS LOW AND ONE COULD
 BE ASSESSED USING ADOPTED STANDARDS BY THE FBC. PLEASE
 REVISE AND ADJUST.
  
 3) NOTE: PLEASE CORRELATE ALL CIRCUITING ON PLANS WITH
 THE SUBMITTED PANEL SCHEDULES. PLEASE BE SURE THE PANEL
 DESIGNATIONS ARE THE SAME.
 PLEASE SEE FOR EXAMPLE: CIRCUIT P-P-20 ON PLANS IS
 SHOWN AS A SPARE 2-POLE 30AMP CIRCUIT ON PANEL *P*>
 PLEASE COORDINATE ALL.
 FBC 106.1.2, 106.3.5.1.2
 NEC 408.4
  
 4) NOTE: PLEASE SEE FBC CHAPTER 13 AND SUBMIT LIGHTING
 POWER DENSITY CALCULATIONS AS STATED IN 13-415.2 FOR
 LIGHTING PERFORMANCE CALCULATIONS.
 PLEASE BE SURE TO SEE FBC 13-415.2.ABC.1.2 FOR TRACK
 LIGHTING CALCULATIONS AND MINIMUM VA TO BE USED FOR
 PERFORMANCE CALCULATIONS.
  
 5) NOTE: PLEASE SHOW LIGHTING CONTROL REQUIREMENTS PER
 13-415.1.ABC.1.2.
 PLEASE ALSO SEE 13-415.1.ABC.1.1.
  
 6) NOTE: PLEASE SEE 600.5 AS THE REQUIRED SIGN CIRCUIT
 SHALL BE DEDICATED AND MAY NOT FEED OTHER ITEMS SUCH AS
 GENERAL RECEPTACLES AS SHOWN ON PLANS.
 PLEASE ALSO SEE THAT THE MINIMUM VA TO BE FIGURED FOR
 CIRCUIT INTO THE LOAD CALCULATIONS IS TO BE 1200VA.
 PLEASE ALSO SEE THAT THE SIGN CIRCUIT IS REQUIRED TO BE
 LOCATED AT THE FRONT ENTRANCE LOCATION.
  
 7) NOTE: PLEASE SEE THE LOAD CALCULATIONS ARE TO MEET
 NEC 220. PLEASE SEE MISSING TRACK LIGHTING CALCULATIONS
 PER 220.43B
 PLEASE SEE THAT ALL CONTINUOUS LOADS INCLUDING THE LOAD
 FOR SIGN CIRCUIT AS NOTED ABOVE SHALL BE FIGURED AT
 125%. THIS IS LIGHTING LOADS.
 215.3, 230.42 ETC.
  
 8) NOTE: PLEASE KNOW THAT ALL LOW VOLTAGE AS SHOWN IS
 REQUIRED TO BE UNDER SEPARATE PERMIT(S). THESE PLANS
 MAY BE USED FOR REFERENCING HOWEVER WILL BE SEPARATE
 PERMITS.
 PLEASE KNOW IF A *SECURITY SYSTEM* SUCH A BURGLAR ALARM
 SYSTEM IS A SEPARATE LV PERMIT FROM THE OTHER LV AS
 SHOWN ON PLANS. (NO PLANS ARE NEEDED FOR BURGLAR
 ALARM.
 CATV< CAMERAS< PHONE MAY BE ON ONE LV PERMIT
 APPLICATION WITH THE EXCEPTION OF BURGLAR ALARM WHICH
 IS SEPARATE.
 THIS IS NOTED FOR INFORMATIONAL PURPOSE ONLY.
  
 9) NOTE: PLEASE PROVIDE THE MINIMUM LIGHTING LEVELS FOR
 STAIRS UNDER NORMAL AND EMERGENCY CONDITIONS PER LIFE
 SAFETY CODE. PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2.
  
 10) NOTE: PLEASE SEE DISCONNECT FOR THE AHU DOES NOT
 MEET 440.11.
 PLEASE RELOCATE.
  
 11) NOTE: PLEASE SEE 13-413.1.ABC.2.2 AND PROVIDE.
  
 ** PLEASE KNOW AS SOME INFORMATION HAS NOT YET BEEN
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]