Plan Review Notes For Permit 07100424 |
Permit Number |
07100424 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-10-29 18:52:36 | *****UNSAT***** | | | | THE PLAN APPEARS TO INDICATE THAT SUITE 100 WILL BE | | SEPARATED INTO TWO UNITS BY A NEW DEMOUNTABLE PARTITION | | WALL.WHAT IS THE | | | | | | 1.ON SHEET LS.1 UNDER THE LIFE SAFETY PLAN, BOTH | | 3/16" = 1.0' AND 3/32" = 1.0' FOR SCALING ARE SHOWN. | | PLEASE EXPLAIN. | | | | 2.THE PLAN APPEARS TO INDICATE THAT SUITE 100 WILL BE | | SEPARATED INTO TWO UNITS BY A NEW DEMOUNTABLE PARTITION | | WALL.WHAT IS THE FIRE RATING FOR THIS WALL? | | | | 3.ON SHEET FA1.1, A FIRE ALARM MANUAL STATION IS | | NOTED IN THE LOBBY (101) ROOM.PLEASE EXPLAIN. | | | | 4.ON SHEET FA1.1, AMEND SHEET NOTE #12 TO REFLECT | | THAT THE FIRE ALARM SYSTEM IS TO BE CLASS A OR FULLY | | ADDRESSABLE. | | | | 5.IFTHE ERECTION/INSTALLATION OF THE NEW PARTITION | | WALL HAVE CAUSE FOR THE FIRE SPRINKLER HEADS OR OTHER | | DEVICES TO BE MODIFIED, SEPARATE PLANS AND PERMIT WILL | | BE REQUIRED FOR THE REMODEL. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|