Plan Review Notes
Plan Review Notes For Permit 07100424
Permit Number 07100424
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-29 18:52:36*****UNSAT*****
  
 THE PLAN APPEARS TO INDICATE THAT SUITE 100 WILL BE
 SEPARATED INTO TWO UNITS BY A NEW DEMOUNTABLE PARTITION
 WALL.WHAT IS THE
  
  
 1.ON SHEET LS.1 UNDER THE LIFE SAFETY PLAN, BOTH
 3/16" = 1.0' AND 3/32" = 1.0' FOR SCALING ARE SHOWN.
 PLEASE EXPLAIN.
  
 2.THE PLAN APPEARS TO INDICATE THAT SUITE 100 WILL BE
 SEPARATED INTO TWO UNITS BY A NEW DEMOUNTABLE PARTITION
 WALL.WHAT IS THE FIRE RATING FOR THIS WALL?
  
 3.ON SHEET FA1.1, A FIRE ALARM MANUAL STATION IS
 NOTED IN THE LOBBY (101) ROOM.PLEASE EXPLAIN.
  
 4.ON SHEET FA1.1, AMEND SHEET NOTE #12 TO REFLECT
 THAT THE FIRE ALARM SYSTEM IS TO BE CLASS A OR FULLY
 ADDRESSABLE.
  
 5.IFTHE ERECTION/INSTALLATION OF THE NEW PARTITION
 WALL HAVE CAUSE FOR THE FIRE SPRINKLER HEADS OR OTHER
 DEVICES TO BE MODIFIED, SEPARATE PLANS AND PERMIT WILL
 BE REQUIRED FOR THE REMODEL.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722