| 2008-03-17 11:19:44 | ** DENIED2ND REVIEW** |
| | |
| | ** PLEASE SEE THE NOTES BELOW WHICH ARE FROM THE FIRST |
| | REVIEW WHICH STILL NEED TO BE ADDRESSED. |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED |
| | ON ELECTRICAL PLANS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SUBMIT COMPLETE LAYOUT OF THE EXISTING |
| | DWELLING SHOWING CURRENT CODE COMPLIANCE FOR SMOKE |
| | ALARMS EXISTING OR NEW TO BE INSTALLED PER FBC R313 |
| | NFPA-72 11.5.1.1.1, 11.8.3 |
| | |
| | 3) NOTE: PLEASE SEE 210.8A7 AS ALL RECEPTACLES |
| | INCLUDING DEDICATED CIRCUITS WHICH ARE 15/20AMP 120V |
| | WITHIN 6FT OF A LAUNDRY SINK SHALL BE GFI/GFI |
| | PROTECTED. |
| | |
| | 4) NOTE: PLEASE SEE WATER HEATER BEING REPLACED DOES |
| | NOT SHOW THE REQUIRED DISCONNECT PER 422.31 |
| | |
| | 5) NOTE: PLEASE INDICATE ON THE NEW PANEL SCHEDULES |
| | SUBMITTED WHICH CIRCUITS ARE NEW AND WHICH ONES ARE |
| | EXISTING. |
| | FBC 106.3.5.4, NEC 408.4 |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |