2007-10-18 08:35:54 
 *** DENIED *****
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODE IS STATED ON
 PLANS.
 2002 NFPA-72.
  
 2) NOTE: PLEASE PROVIDE A LAYOUT OF THE EXISTING
 DWELLING WHICH SHOWS EITHER EXISTING SMOKE ALARMS
 MEETING NFPA-72 OR NEW TO BE INSTALLED.
 PLEASE SEE FBC R313 AND NFPA-72 11.5.1.1.1, 118.3
  
 3) NOTE: PLEASE SEE THE FOLLOWING ITEMS WHICH REQUIRE
 DISCONNECTS ARE INDICATING 240V RECEPTACLE OUTLETS ON
 PLANS.
 CONDENSING UNIT MISSING DISCONNECT PER 440.11.
 TANKLESS WATER HEATER MISSING DISCONNECT PER
 422.30/422.31.
 AIR HANDLER UNIT MISSING DISCONNECT PER 440.11
  
 4) NOTE: CONDENSING UNIT MISSING GFI PER 210.63, 210.8
  
 5) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS
 FOR THE NEW TANKLESS WATER HEATER. PLEASE KNOW THERE
 ARE SEVERAL OF THESE UNITS ON THE MARKET WHICH ARE NOT
 A LISTED PRODUCT BY ANY NRTL. (NATIONALLY RECOGNIZED
 TESTING LABORATORY). IE UL, ETL, CSA, TUV, MET ETC.
 90.7, 110.3
 FBC106.1.2
  
 6) NOTE: PLEASE CLARIFY THE RISER AS SHOWN AS THE PLANS
 CALL FOR THIS AS BEING EXISTING YET THE PLANS DO NOT
 SHOW THE MAIN DISCONNECT AS SHOWN ON RISER.
 PLEASE ALSO VERIFY THE CONDUCTORS AS SHOWN ON RISER.
 THIS SHOWS 4/0 AS THE SERVICE ENTRANCE CONDUCTORS AND
 THEN 2/0 TO THE 150 PANEL. THE CONDUCTORS SIZES AS
 SHOWN ARE HIGHER THAN NORMAL AND ARE OK, HOWEVER IF
 SHOWN AS THIS SIZE, THIS IS WHAT WILL BE REQUIRED TO BE
 INSTALLED.
 PLEASE ALSO CLARIFY WHERE THE EXISTING PANEL FOR HOUSE
 IS. AS THE RISER SHOWS THIS PANEL AS NEW, IT IS NOT
 CLEAR WHAT EXISTS AND WHICH IS NEW.
  
 7) NOTE: PLEASE SEE THE MINIMUM WORKING CLEARANCES FOR
 THE TANK-LESS WATER HEATER NEEDS TO BE MET. THE
 LOCATION AND SPACE AS SHOWN ON PLANS DO NOT SEEM TO
 INDICATE ENOUGH CLEARANCES.
 110.3, SEE ALSO MANUFACTURES SPECS/CUT SHEETS FOR
 UNIT.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved