| 2007-10-18 08:35:54 | |
| | *** DENIED ***** |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING CODE IS STATED ON |
| | PLANS. |
| | 2002 NFPA-72. |
| | |
| | 2) NOTE: PLEASE PROVIDE A LAYOUT OF THE EXISTING |
| | DWELLING WHICH SHOWS EITHER EXISTING SMOKE ALARMS |
| | MEETING NFPA-72 OR NEW TO BE INSTALLED. |
| | PLEASE SEE FBC R313 AND NFPA-72 11.5.1.1.1, 118.3 |
| | |
| | 3) NOTE: PLEASE SEE THE FOLLOWING ITEMS WHICH REQUIRE |
| | DISCONNECTS ARE INDICATING 240V RECEPTACLE OUTLETS ON |
| | PLANS. |
| | CONDENSING UNIT MISSING DISCONNECT PER 440.11. |
| | TANKLESS WATER HEATER MISSING DISCONNECT PER |
| | 422.30/422.31. |
| | AIR HANDLER UNIT MISSING DISCONNECT PER 440.11 |
| | |
| | 4) NOTE: CONDENSING UNIT MISSING GFI PER 210.63, 210.8 |
| | |
| | 5) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS |
| | FOR THE NEW TANKLESS WATER HEATER. PLEASE KNOW THERE |
| | ARE SEVERAL OF THESE UNITS ON THE MARKET WHICH ARE NOT |
| | A LISTED PRODUCT BY ANY NRTL. (NATIONALLY RECOGNIZED |
| | TESTING LABORATORY). IE UL, ETL, CSA, TUV, MET ETC. |
| | 90.7, 110.3 |
| | FBC106.1.2 |
| | |
| | 6) NOTE: PLEASE CLARIFY THE RISER AS SHOWN AS THE PLANS |
| | CALL FOR THIS AS BEING EXISTING YET THE PLANS DO NOT |
| | SHOW THE MAIN DISCONNECT AS SHOWN ON RISER. |
| | PLEASE ALSO VERIFY THE CONDUCTORS AS SHOWN ON RISER. |
| | THIS SHOWS 4/0 AS THE SERVICE ENTRANCE CONDUCTORS AND |
| | THEN 2/0 TO THE 150 PANEL. THE CONDUCTORS SIZES AS |
| | SHOWN ARE HIGHER THAN NORMAL AND ARE OK, HOWEVER IF |
| | SHOWN AS THIS SIZE, THIS IS WHAT WILL BE REQUIRED TO BE |
| | INSTALLED. |
| | PLEASE ALSO CLARIFY WHERE THE EXISTING PANEL FOR HOUSE |
| | IS. AS THE RISER SHOWS THIS PANEL AS NEW, IT IS NOT |
| | CLEAR WHAT EXISTS AND WHICH IS NEW. |
| | |
| | 7) NOTE: PLEASE SEE THE MINIMUM WORKING CLEARANCES FOR |
| | THE TANK-LESS WATER HEATER NEEDS TO BE MET. THE |
| | LOCATION AND SPACE AS SHOWN ON PLANS DO NOT SEEM TO |
| | INDICATE ENOUGH CLEARANCES. |
| | 110.3, SEE ALSO MANUFACTURES SPECS/CUT SHEETS FOR |
| | UNIT. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |