Plan Review Notes
Plan Review Notes For Permit 07100380
Permit Number 07100380
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-18 08:57:26 
 *** DENIED *****
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SUBMIT TWO SETS OF PLANS WHICH ARE
 DRAWN WITH MINIMUM REQUIREMENTS FOR CONSTRUCTION
 DOCUMENTS PER FBC 106.1.
 PLEASE SEE ONLY ONE SET OF ELECTRICAL PLANS WERE
 SUBMITTED AND THEY DO NOT CORRELATE WITH THE FLOOR PLAN
 SUBMITTED WITH THIS PERMIT NOR DO THEY CORRELATE WITH
 THE FLOOR PLAN ON THE PLANS WHICH WERE SUBMITTED FOR
 BUILDING PERMITS.
 FOR EXAMPLE, ONLY ONE LAVATORY SHOWN IN BATHROOM ON ONE
 DRAWING AND TWO SHOWN IN ANOTHER, THE CLOSET LAYOUTS DO
 NOT CORRELATE, WALLS, ETC.
 PLEASE COORDINATE AND SUBMIT PLANS. THESE MAY NOT BE
 DONE IN PENCIL AND RED PEN.
  
 3) NOTE: PLANS INDICATE A *SD* WHICH IS FOR SMOKE
 DETECTOR. IF THIS IS A SMOKE DETECTOR BY DEFINITION IN
 NFPA-72 PLEASE INDICATE THE FIRE ALARM PANEL, SOUNDING
 DEVICE(S) ETC.
 IF THIS IS A SMOKE ALARM, PLEASE COMPLETE PLANS AS
 SUCH.
 PLEASE SHOW NEW OR EXISTING MEETING NFPA-72 11.5.1.1,
 11.8.3
  
 4) NOTE: PLEASE INDICATE THE MINIMUM REQUIRED
 CIRCUIT(S) PER 210.11C3, 210.52 FOR BATH(S).
 MUST BE #12 AND 20AMP MIN.
  
 5) NOTE: PLEASE INDICATE THE MINIMUM CIRCUITS FOR
 JACUZZI TUB. WHAT SIZE OVER CURRENT PROTECTION, WHAT
 SIZE CONDUCTORS ETC.
 CLARIFY TWO GFI RECEPTACLES BEING SHOWN FOR THE ONE
 JACUZZI. IF THIS CONTAINS A HEATING UNIT, PLEASE ADJUST
 CALCULATIONS, PANEL SCHEDULE AND CIRCUITING.
 240.4, 310.16, 408.4
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE KNOW THAT EVEN WHEN PLANS ARE PERMITTED
 TO FALL UNDER THE EXCEPTIONS OF 481/471 FOR PLANS, THE
 PLANS STILL MUST CONTAIN A PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE.
 FBC 106.1.2, 106.3.5
 PLEASE BE SURE TO GET WITH THE BUILDING CONTRACTOR TO
 COORDINATE PLANS AS THE REVIEW UNDER THE BUILDING
 PERMIT HAS BEEN FAILED BASED ON THESE PLANS AND THE
 PLANS SUBMITTED BY THE BUILDING CONTRACTOR.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]