| 2007-10-18 08:57:26 | |
| | *** DENIED ***** |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SUBMIT TWO SETS OF PLANS WHICH ARE |
| | DRAWN WITH MINIMUM REQUIREMENTS FOR CONSTRUCTION |
| | DOCUMENTS PER FBC 106.1. |
| | PLEASE SEE ONLY ONE SET OF ELECTRICAL PLANS WERE |
| | SUBMITTED AND THEY DO NOT CORRELATE WITH THE FLOOR PLAN |
| | SUBMITTED WITH THIS PERMIT NOR DO THEY CORRELATE WITH |
| | THE FLOOR PLAN ON THE PLANS WHICH WERE SUBMITTED FOR |
| | BUILDING PERMITS. |
| | FOR EXAMPLE, ONLY ONE LAVATORY SHOWN IN BATHROOM ON ONE |
| | DRAWING AND TWO SHOWN IN ANOTHER, THE CLOSET LAYOUTS DO |
| | NOT CORRELATE, WALLS, ETC. |
| | PLEASE COORDINATE AND SUBMIT PLANS. THESE MAY NOT BE |
| | DONE IN PENCIL AND RED PEN. |
| | |
| | 3) NOTE: PLANS INDICATE A *SD* WHICH IS FOR SMOKE |
| | DETECTOR. IF THIS IS A SMOKE DETECTOR BY DEFINITION IN |
| | NFPA-72 PLEASE INDICATE THE FIRE ALARM PANEL, SOUNDING |
| | DEVICE(S) ETC. |
| | IF THIS IS A SMOKE ALARM, PLEASE COMPLETE PLANS AS |
| | SUCH. |
| | PLEASE SHOW NEW OR EXISTING MEETING NFPA-72 11.5.1.1, |
| | 11.8.3 |
| | |
| | 4) NOTE: PLEASE INDICATE THE MINIMUM REQUIRED |
| | CIRCUIT(S) PER 210.11C3, 210.52 FOR BATH(S). |
| | MUST BE #12 AND 20AMP MIN. |
| | |
| | 5) NOTE: PLEASE INDICATE THE MINIMUM CIRCUITS FOR |
| | JACUZZI TUB. WHAT SIZE OVER CURRENT PROTECTION, WHAT |
| | SIZE CONDUCTORS ETC. |
| | CLARIFY TWO GFI RECEPTACLES BEING SHOWN FOR THE ONE |
| | JACUZZI. IF THIS CONTAINS A HEATING UNIT, PLEASE ADJUST |
| | CALCULATIONS, PANEL SCHEDULE AND CIRCUITING. |
| | 240.4, 310.16, 408.4 |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 6) NOTE: PLEASE KNOW THAT EVEN WHEN PLANS ARE PERMITTED |
| | TO FALL UNDER THE EXCEPTIONS OF 481/471 FOR PLANS, THE |
| | PLANS STILL MUST CONTAIN A PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE. |
| | FBC 106.1.2, 106.3.5 |
| | PLEASE BE SURE TO GET WITH THE BUILDING CONTRACTOR TO |
| | COORDINATE PLANS AS THE REVIEW UNDER THE BUILDING |
| | PERMIT HAS BEEN FAILED BASED ON THESE PLANS AND THE |
| | PLANS SUBMITTED BY THE BUILDING CONTRACTOR. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |