| Date |
Text |
| 2007-10-30 09:18:55 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| | ** FLORIDA STATUTES (FS). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | **NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE CORRESPONDING |
| | LENGTHS INDICATED. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | **NOTE: NOT ALL PIPING MATERIALS AND SIZES ARE |
| | INDICATED ON THE DRAWINGS. PLEASE CLARIFY ON THE |
| | RESUBMITTAL IF THE STEEL RISER INDICATED ON THE |
| | DRAWINGS IS SCH. 40 BLACK STEEL OR SCH. 40 GALVANIZED |
| | PIPE. |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | **NOTE: EVEN FUTURE APPLIANCES NEED A BTU LOAD. PLEASE |
| | INDICATE A BTU LOAD FOR THE FUTURE BBQ ON THE |
| | RESUBMITTAL. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | **NOTE: THIS COMMENT GOES ALONG WITH COMMENT #1, A PLAN |
| | REVIEW CAN NOT BE DONE WITHOUT THIS INFORMATION. GAS |
| | SYSTEMS ARE SIZED BY THE LONGEST LENGTH METHOD PER |
| | *402.4.1. |
| | |
| | 5. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | **NOTE: PLAN REVIEW CAN NOT BE DONE WITHOUT THIS |
| | INFORMATION. |
| | |
| | 6. PLEASE CLARIFY THE FOLLOWING ON THE PROPOSED GAS |
| | PLANS "NOTE: 1/2 SYSTEM". WHAT DOES THAT MEAN? IS ONLY |
| | 1/2 OF THE GAS SYSTEM BEING INDICATED ON THESE |
| | SUBMITTED DRAWINGS? |
| | |
| | 7. THE REFERENCED GENERATOR FOR THE PROPOSED GAS |
| | SYSTEM WILL NEED A SEPERATE PERMIT. PLEASE REFERENCE |
| | THE RESIDENTIAL GENERATOR PLAN REVIEW REQUIREMENTS |
| | ATTACHED TO THESE GAS COMMENTS. A GAS PERMIT CAN NOT BE |
| | ISSUED UNTIL A GEN/RES PERMIT APPLICATION HAS BEEN |
| | APPLIED FOR AND APPROVED BY ZONING FOR THE GENERATOR |
| | LOCATION. |
| | |
| | ******IMPORTANT INFORMATION****** |
| | AS OF 8/25/06 GENERATOR (GEN/RES AND |
| | GEN/COM) PERMIT APPLICATIONS SHALL NOT |
| | BE ACCEPTED UNLESS THE ELECTRICAL INFOR- |
| | MATION AND GAS (OR DIESEL) INFORMATION |
| | IS ALL SUBMITTED AT THE SAME TIME. THE |
| | GENERATOR, ELECTRICAL AND GAS/DIESEL IN- |
| | FORMATION WILL BE ROUTED TOGETHER. THIS |
| | WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY |
| | THE MANUFACTURER'S SPECI- |
| | FICATIONS AND INSTALLATION INSTRUCTIONS) |
| | ARE AVAILABLE TO ALL PLAN REVIEWERS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |