| Plan Review Notes For Permit 07100370 |
| Permit Number |
07100370 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-16 13:56:49 | 2004 FBC W/2007 REVISIONS | | | REROOF 6/12 AND FLAT | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS FROM A | | | FLORIDA LICENSED ENGINEER OR ARCHITECT AS REQUIRED BY | | | LIMITATION #7 ON PAGE 44 OF THE NOA FOR THE POLYGLAS | | | MODIFIED ROOFING SYSTEM. ENHANCED FASTENING IS REQUIRED | | | IN THE CORNER AREAS PER FBC TABLE 1609.6.2.1(2). | | | | | | 2) SUBMIT PRODUCT APPROVALS FOR THE SECONDARY WATER | | | BARRIER THAT WILL BE INSTALLED AS REQUIRED PURSUANT TO | | | FS 553.844. | | | | | | - ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] | | | |
|