Date Text
2007-10-16 10:30:112004 FBC W/2007 REVISIONS
 REROOF WITH METAL ROOF
  
 DENIED BY BUILDING
  
 1) THE PRODUCT APPROVAL FOR THE SOUTHEASTERN 5V-CRIMP
 METAL ROOF SYSTEM HAS A MAXIMUM UPLIFT DESIGN PRESSURE
 OF -57.5 PSF WITH NO ENHANCED FASTENING ALLOWED. THIS
 PRESSURE IS TOO LOW FOR THE CORNER AREAS WHICH REQUIRE
 -83.1 PSF PER FBC TABLE 1609.6.2.1(2).
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW