| Plan Review Notes For Permit 07100361 |
| Permit Number |
07100361 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-08-05 15:24:17 | ****************PROVISO***************** | | | A} PER FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE | | | SECTION 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING | | | FOUNTAIN IS PROVIDED ON A FLOOR, THERE SHALL BE A | | | DRINKING FOUNTAIN WHICH IS ACCESSIBLE TO INDIVIDUALS | | | WHO USE WHEELCHAIRS IN ACCORDANCE WITH SECTION 11-4.15 | | | AND ONE ACCESSIBLE TO THOSE WHO HAVE DIFFICULTY BENDING | | | OR STOOPING.(THIS CAN BE ACCOMMODATED BY THE USE OF A | | | HI-LO FOUNTAIN OR BY SUCH OTHER MEANS AS WOULD ACHIEVE | | | THE REQUIRED ACCESSIBILITY FOR EACH GROUP ON EACH | | | FLOOR). | | | | | | B} A CLEANOUT IS REQUIRED AT THE BASE OF THE DRINKING | | | FOUNTAIN WASTE STACK. PER FBC-2004 PLUMBING SECTION | | | 708.3.5 BASE OF STACK. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|