| 2008-01-17 14:51:14 | DENIED; | | | PLUMBING PLAN REVIEW COMMENTS FROM 1/2/08 HAVE NOT BEEN | | | ADDRESSED; | | | 1. NO; PLANS DO NOT SHOW REQUIRED DRINKING FOUNTAIN. | | | SEE TABLE 403.1 2004 FBC-PLUMBING. | | | 2. NO; SHOW A DETAIL OF SINK WITH ALL REQUIRED | | | MESSUREMENTS TO COMPLY WITH FBC-BUILDING CHAPTER 11, | | | SECTIONS 11-4.24.1 THRU 11-4.24.7. | | | 3. NO; SANITARY RISER DIAGRAM IS REQUIRED SEE | | | FBC-BUILDING CHAPTER 1 ADMINISTRATION CODE SECTION | | | 106.3.5.1.3 (13). | | | A COPY OF FIRST REVIEW IS ATTACHED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|