| 2008-01-23 13:37:32 | *****DENIED***** |
| | |
| | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE |
| | PLAN REVIEW STILL NEED TO BE ADDRESSED: |
| | |
| | 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 02.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE |
| | WITH EMERGENCY RESPONSE TO THE PROPERTY OR VICINITY |
| | THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES). |
| | |
| | 03.COMBUSTIBLE WASTE MATERIALS SHALL BE REMOVED FROM |
| | THE SITE AT THE END OF EACH SHIFT OR MORE FREQUENTLY AS |
| | NECESSARY FOR SAFE OPERATION. |
| | |
| | 04.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 05.DUE TO THE CHANGE IN OCCUPANCY, THE DIMENSION OF |
| | THE ADDRESS NUMBER SHALL BE NO LESS THAN 6" IN HEIGHT |
| | AND NO LESS THAN 1" IN WIDTH.PLEASE SHOW THE ADDRESS |
| | NUMBERS ON THE APPROPIATE EXTERIOR ELEVATION WHICH |
| | FRONTS WESTMINISTER PLACE. |
| | |
| | 06.PROVIDE THE OCCUPANT LOAD (NUMBER OF PERSONS FOR |
| | WHOM MEANS OF EGRESS AND OTHER PROVISIONS ARE REQUIRED) |
| | BASED UPON THE CHARACTERISTICS OF THE USE OF THE SPACE |
| | OR AS DETERMINED AS THE MAXIMUM PROBABLE POPULATION OF |
| | THE SPACE UNDER CONSIDERATION, WHICHEVER IS GREATER. |
| | |
| | 07. PLEASE SHOW EXISTING LAYOUT OF THE STRUCTURE AS TO |
| | BE COMPARED TO THE PROPOSED LAYOUT DETAILING THE SCOPE |
| | OF WORK (CONVERSION FROM A RESIDENTIAL OCCUPANCY TO A |
| | NEW BUSINESS OCCUPANCY). |
| | |
| | 08.SPECIFY INTERIOR WALL AND CEILING FINISH MATERIALS |
| | IN TERMS OF CLASS A, CLASS B, OR CLASS C.SPECIFY |
| | INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II. |
| | |
| | 09.PROVIDE LIFE SAFETY PLAN CRITERIA SHOWING TRAVEL |
| | DISTANCE TO REACH EXIT(S).THE LOCATION OF EXIT LIGHTS |
| | AND EMERGENCY LIGHTS MAY ALSO BE SHOWN. |
| | |
| | 10.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE |
| | EXTINGUISHER(S) WHICH SATISFY THE 75 FEET TRAVEL |
| | DISTANCE. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE EACH ITEM AWAS ADDRESSED |
| | |
| | |