| 2008-01-03 11:50:08 | BUILDING PLAN REVIEW |
| | PERMIT: 07100361 |
| | ADD: 339 WESTMINSTER PL |
| | CONT: BATTEN CONST. |
| | TEL: (561)820-0027 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | 1-2-08 |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 2)2004 FBC EXISTING 301.5. A DESIGN PROFESSIONAL OR |
| | AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| | THIS CODE. |
| | |
| | 3)THE CERTIFICATE OF AUTHORIZATION FOR BROWER |
| | ARCHITECTURE ASSOCIATES INC SHALL BE INDICATED ON EACH |
| | SHEET PER F.S 481.219 AND F.A.C. 61G1-16.004. THE TITLE |
| | BLOCK FOR ANY SHEET BEARING THE NAME OF AN ARCHITECT |
| | PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A |
| | PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES, SHALL |
| | INCLUDE A VALID CERTIFICATE OF AUTHORIZATION NUMBER. |
| | |
| | 4)AN EXISTING AND A PROPOSED FLOOR PLAN SHALL BE |
| | SUBMITTED SHOWING THE CHANGES TO EACH WALL AND ROOM. A |
| | WALL LEGEND SHALL BE PROVIDED SHOWING EACH NEW WALL, |
| | EXISTING WALL TO BE DEMOED AND REMAINING WALLS. THE |
| | FLOOR PLAN SHALL CONSIST OF THE ENTIRE STRUCTURE FOR |
| | THE EXISTING AND THE PROPOSED. A DETAIL OF EACH WALL |
| | WITH ALL MATERIALS, STUD SPACING AND UL NUMBER IS |
| | REQUIRED.THE PLANS SHALL INDICATE THE TYPE OF |
| | CONSTRUCTION AS DEFINED IN CHAPTER 6, TABLE 601/ THE |
| | USE AND OCCUPANCY IN ACCORDANCE WITH THE PROVISIONS OF |
| | CHAPTER 3 AND THE OCCUPANT LOAD SEE 1004. THE BUILDING |
| | OFFICIAL MAY REQUIRE ADDITIONAL INFORMATION DUE TO THE |
| | CHANGE OF OCCUPANCY. W.P.B AMENDMENTS 106.1.2 |
| | |
| | 5)A LIFE SAFETY PLAN SHALL BE SUBMITTED SHOWING THE |
| | MEANS OF EGRESS WHICH SHALL INCLUDE EXIT, EXIT ACCESS |
| | AND EXIT DISCHARGE. |
| | |
| | 6)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION; |
| | PROVIDE INFORMATION BASED ON INTERIOR FINISH |
| | REQUIREMENTS BASED ON OCCUPANCY. PROVIDE A FINISH |
| | SCHEDULE INDICATING THE FINISH IN EACH ROOM. |
| | |
| | 7)SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE |
| | MOUNTED WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE |
| | FINISH FLOOR. 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST |
| | 27" HIGH 30" WIDE, AND 19" DEEP SHALL BE PROVIDED |
| | UNDERNEATH SINKS. 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR |
| | FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES (760 MM BY |
| | 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE |
| | PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD APPROACH. |
| | THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE |
| | AND SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM) |
| | UNDERNEATH THE SINK. PROVIDE ELEVATION DRAWINGS SHOWING |
| | COMPLIANCE. |
| | |
| | 8)ON THE DRAWINGS SHOW CLEARLY THESE REQUIREMENTS FOR |
| | THE RAMP. 11-4.8.4. (2) LANDINGS. ALL LANDINGS ON RAMPS |
| | SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH |
| | RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL |
| | CLEARANCE. 11-4.8.4(3) IF RAMPS CHANGE DIRECTION AT |
| | LANDINGS, THE MINIMUM LANDING SIZE SHALL BE 60" X 60". |
| | 11.4.8.5. HANDRAILS: IF A RAMP HAS A RISE GREATER THAN |
| | 6" OR A HORIZONTAL PROJECTION GREATER THAN 72", THEN IT |
| | SHALL HAVE HANDRAILS ON BOTH SIDES. |
| | |
| | 9)AT LEAST ONE ACCESSIBLE ROUTE WITHIN THE BOUNDARY |
| | OF THE SITE SHALL BE PROVIDED FROM PUBLIC |
| | TRANSPORTATION STOPS, ACCESSIBLE PARKING, AND |
| | ACCESSIBLE PASSENGER LOADING ZONES, AND PUBLIC STREETS |
| | OR SIDEWALKS TO THE ACCESSIBLE BUILDING ENTRANCE THEY |
| | SERVE. THE ACCESSIBLE ROUTE SHALL, TO THE MAXIMUM |
| | EXTENT FEASIBLE, COINCIDE WITH THE ROUTE FOR THE |
| | GENERAL PUBLIC. FBC.11-4.3.2. |
| | |
| | 10)THE DRAWINGS SHALL SHOW THE ACCESSIBLE PARKING FOR |
| | THE BUILDING, WHICH SHALL BE LOCATED ON THE SHORTEST |
| | SAFELY ACCESSIBLE ROUTE OF TRAVEL FROM THE PARKING LOT |
| | TO THE ENTRANCE TO THE BUILDING. 11-4.6.2. |
| | |
| | 11)THE DRAWINGS MAKE REFERENCES TO DETAILS WHICH ARE |
| | NOT SUBMITTED E.G. A2.03 / A2.02. THE DRAWINGS ALSO |
| | MAKE REFERENCE TO NEW SITE WALL; HOWEVER, THERE IS NO |
| | INFORMATION OR DETAILS OF THE NEW WALL ON THE PLANS. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS. FBC 106.1.1. |
| | |
| | 12)BEFORE A PERMIT TO CONSTRUCT MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY.THE ACTUAL |
| | PERMIT PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY |
| | OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561) 233-5025 FOR MORE INFORMATION. |
| | |
| | 13)FBC 1210.2 WALLS WITHIN 2 FEET OF URINALS AND |
| | WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT |
| | SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE FLOOR. |
| | |
| | 14)ALL DOORS TO ACCESSIBLE TOILET ROOMS SHALL COMPLY |
| | WITH SECTION 11-4.13. DOORS SHALL NOT SWING INTO THE |
| | CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE. FBC |
| | 11-4.22.2. |
| | |
| | 15)THERE IS NO RECORD FOR THE INTERIOR MODIFICATION |
| | OF THE EXISTING STRUCTURE; THEREFORE PLANS SHALL BE |
| | SUBMITTED FOR THE REMODEL WORK. A FAIR MARKET VALUE |
| | SHALL BE INDICATED ON THE PERMIT APPLICATION. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |