2008-01-02 08:02:59DENIED;
 1.FBC-PLUMBING TABLE 403.1 MINIMUM PLUMBING
 REQUIREMENTS REQUIRES A DRINKING FOUNTAIN. THE DRINKING
 FOUNTAIN SHALL MEET THE REQUIREMENTS OF FBC-BUILDING
 CHAPTER 11 SECTIONS 11-4.15.1 THRU 11-4.15.5. SHOW A
 DETAIL ON PLANS WITH ALL REQUIRED MEASUREMENTS AND SHOW
 CLEAR FLOOR SPACE REQUIRED.
 2. DUE TO CHANGE OF OCCUPENCY THE KITCHEN BECOMES A
 COMMON AREA AND THE SINK IS REQUIRED TO MEET THE
 REQUIREMENTS OF BUILDING CHAPTER 11 SECTIONS 11-4.24.1
 THRU 11-4.24.7. SHOW A DETAIL ON PLANS WITH ALL
 REQUIRED MEASUREMENTS AND SHOW THE CLEAR FLOOR SPACE ON
 PLANS.
 3. DUE TO THE REQUIREMENTS FOR A DRINKING FOUNTAIN A
 SANITARY RISER DIAGRAM IS REQUIRED, SEE AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 2004 EDITION SECTION 106.3.5.1.3(13).