| Plan Review Notes For Permit 07100361 |
| Permit Number |
07100361 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-31 14:29:03 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1}7.8 ILLUMINATION OF MEANS OF EGRESS, INDICATE | | | COMPLIANCE FOR SAME. 7.8 NFPA-101 | | | | | | 2} INDICATE COMPLIANCE WITH 13-415.2ABC.1, PERFORMANCE | | | CALCULATION PROCEDURES. SUBMIT FORMS WITH 13-415.2B OR | | | 13-415.2.C.1 DENSITIES. DENSITY AND LIGHTING CONTROLS | | | MUST BE SUBMITTED FOR REVIEW, AND THE FIXTURE SCHEDULE | | | MUST AGREE. 13-101.6 BUILDING SYSTEMS.THERMAL | | | EFFICIENCY STANDARDS ARE SET FOR THE FOLLOWING BUILDING | | | SYSTEMS WHERE NEW PRODUCTS ARE INSTALLED OR REPLACED IN | | | EXISTING BUILDINGS, AND FOR WHICH A PERMIT MUST BE | | | OBTAINED. SUCH SYSTEMS SHALL MEET THE MINIMUM | | | EFFICIENCIES ALLOWED FOR THAT SYSTEM ON FORM 400C FOR | | | COMMERCIAL BUILDINGS AND ON FORM 600C FOR RESIDENTIAL | | | BUILDINGS. | | | | | | 3} THE ARCHITECTURAL FIRM MUST DISPLAY THE CERTIFICATE | | | OF AUTHORIZATION ON THE TITLE BLOCK PER 481.221 (8). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|