Plan Review Notes
Plan Review Notes For Permit 07100355
Permit Number 07100355
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-24 14:08:04 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} HAND DRAWN PLANS IN PENCIL ARE NOT ACCEPTABLE FOR
 RECORD RETENTION OR CLARITY IN THE FIELD. 106.1.3 FBC
 AS AMENDED.
  
 2} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 3} THE SCOPE OF WORK ON THEAPPLICATION INDICATES
 REPLACING THE DISCONNECT, BUT A COMPLETE REWIRE WAS
 SUBMITTED. IF THE REWIRE IS TO BE PART OF THIS PERMIT,
 CHANGE THE SCOPE ON THE APPLICATION TO REFLECT SAME AND
 INCREASE THE PROJECT VALUE TO ENCOMPASS ALL WORK.
  
 4} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 5 } PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE TO THE
 EQUIPMENT TO BE INSTALLED. SEE METER TO DISCONNECT ON
 RISER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]