| 2007-11-10 07:36:54 | BUILDING PLAN REVIEW |
| | PERMIT: 07100326 |
| | ADD: 1801 S. FLAGLER DR. #302 |
| | CONT: RCX TILT UP CONSTRUCTION INC. |
| | TEL: (561)386-6032 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 2ND |
| | ACTION: DENIED |
| | **NO RESPONSE NOT ADDRESSED** |
| | 1)WPB AMENDMENTS 106.1.2PROVIDE A FRAMING WALL |
| | DETAIL FOR THE NEW WALL. THE BUILDING OFFICIAL MAY |
| | REQUIRE DETAILS AND OTHER DATA NECESSARRY TO DESCRIBE |
| | THE CONSTRUCTION OF THE PROJECT. INDICATE THE STUD |
| | SPACING AND ALL MATERIALS FOR THE NEW WALL.IF ANY |
| | PORTION OF THE TENANT SEPERATION WALL IS DEMOED, |
| | CLEARLY INDICATE HOW THE RATING OF THE NEW WALL WILL |
| | MEET THE TENANT SPEREATION REQUIREMENTS. PER FBC 708. |
| | ******************************************************* |
| | |
| | **A UL ASSEMBLY OF THE NEW FRAME WALLS SHALL BE |
| | INDICATED ON THE PLANS.** WHAT TYPE OF MATERIALS WILL |
| | BE USE TO CONSTRUCT THEOPENING FOR THE NEW DOOR. |
| | SUBMIT AN EXISTING AND PROPOSED LAYOUT OF THE AREA OF |
| | PRPOPOSED WORK. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THE CODE. FBC. |
| | 106.1.1 |
| | |
| | **A CROSS SECTION DETAIL DRAWING OF THE NEW SHOWER |
| | FLOOR IS REQUIRED TO SHOW THE MATERIALS AND THE |
| | CONSTRUCTION OF THE FLOOR. IS THE 3/4 INCH FIRE RATED |
| | PLYWOOD USED TO CONSTRUT THE SHOWER FLOOR?** |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |