2007-11-10 07:36:54BUILDING PLAN REVIEW
 PERMIT: 07100326
 ADD: 1801 S. FLAGLER DR. #302
 CONT: RCX TILT UP CONSTRUCTION INC.
 TEL: (561)386-6032
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
 **NO RESPONSE NOT ADDRESSED**
 1)WPB AMENDMENTS 106.1.2PROVIDE A FRAMING WALL
 DETAIL FOR THE NEW WALL. THE BUILDING OFFICIAL MAY
 REQUIRE DETAILS AND OTHER DATA NECESSARRY TO DESCRIBE
 THE CONSTRUCTION OF THE PROJECT. INDICATE THE STUD
 SPACING AND ALL MATERIALS FOR THE NEW WALL.IF ANY
 PORTION OF THE TENANT SEPERATION WALL IS DEMOED,
 CLEARLY INDICATE HOW THE RATING OF THE NEW WALL WILL
 MEET THE TENANT SPEREATION REQUIREMENTS. PER FBC 708.
 *******************************************************
  
 **A UL ASSEMBLY OF THE NEW FRAME WALLS SHALL BE
 INDICATED ON THE PLANS.** WHAT TYPE OF MATERIALS WILL
 BE USE TO CONSTRUCT THEOPENING FOR THE NEW DOOR.
 SUBMIT AN EXISTING AND PROPOSED LAYOUT OF THE AREA OF
 PRPOPOSED WORK. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THE CODE. FBC.
 106.1.1
  
 **A CROSS SECTION DETAIL DRAWING OF THE NEW SHOWER
 FLOOR IS REQUIRED TO SHOW THE MATERIALS AND THE
 CONSTRUCTION OF THE FLOOR. IS THE 3/4 INCH FIRE RATED
 PLYWOOD USED TO CONSTRUT THE SHOWER FLOOR?**
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]