| 2008-01-30 16:54:35 | PROJECT: 1801 CONSULATE PLACE #201 |
| | |
| | CODE REVIEW: |
| | 2004 FLORIDA EXISTING BUILDING CODE W/2006 REVISIONS |
| | 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS |
| | CITY OF WEST PALM BEACH ADMINISTRATION AMENDMENTS, |
| | CHAPTER 1, 2004 EDITION |
| | |
| | STATUS: FAILED |
| | |
| | COMMENTS: |
| | |
| | 1) REQUIRE A NOTICE OF COMMENCEMENT AS PER THE |
| | FOLLOWING: |
| | |
| | FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 2) PLEASE INDICATE THE LEVEL OF ALTERATION AS PER THE |
| | FOLLOWING: |
| | |
| | FLORIDA EXISTING BUILDING CODE, SECTION301.5 :A |
| | DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A |
| | COMBINATION OF |
| | LEVELS OF ALTERATION PURSUANT TO SECTION 303,304 & 305 |
| | OF THIS CODE. |
| | |
| | 3) PLEASE INDICATE ON FLOOR PLAN:NEW WALLS/EXISTING |
| | WALLS. |
| | |
| | 4) PLEASE PROVIDE PRODUCT APPROVALS FOR THE INDICATED |
| | SLIDING GLASS DOORS. |
| | |
| | 5) THE PRESCRIPTIVE FIRE RESISTANCE INDICATED ON THE |
| | TWO HOUR RATED WALL DOES NOT REFLECT THE DATA SHOWN BY |
| | TABLE 720.1(2)#13-1.3. |
| | PLEASE CORRECT THE SAME OR INDICATE A TESTED AND |
| | APPROVED RATED ASSEMBLY. |
| | |
| | 6) PLEASE PROVIDE INTERIOR DIMENSIONS AND SQUARE |
| | FOOTAGE. |
| | |
| | 7) PLEASE PROVIDE ENERGY CALCULATIONS AS PER THE |
| | FOLLOWING: |
| | |
| | 512.1MINIMUM REQUIREMENTS. |
| | ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY WITH |
| | THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | END COMMENTS |
| | |
| | PLAN REVIEW: KEN CONRAD |
| | PHONE: 561.805.6666 |
| | E-MAIL: KCONRAD @WPB.ORG |