| 2008-01-22 14:36:02 | |
| | |
| | ** DENIEDREVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED |
| | ON PLANS FOR RELEVANT DESIGN. |
| | FBC 2004 W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE FS 481.219 FOR POSSIBLE FICTITIOUS |
| | NAME FOR ARCHITECT. |
| | PLEASE COMPLETE INFORMATION ON TITLE BLOCKS PER FAC |
| | 61G1-16.004 |
| | |
| | 3) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE PANEL SCHEDULE. |
| | PLEASE SEE 240.4, 310.16, 408.4 |
| | FBC 106.3.5.1.2 (ADDITIONAL INFORMATION). |
| | |
| | 4) NOTE: PLEASE SEE SOME CIRCUITS ON PANEL SCHEDULE AS |
| | SHOWN DO NOT COMPLY WITH THE NEC. FOR EXAMPLE: PLEASE |
| | SEE WATER HEATER WHICH IS SHOWN AS 4500VA LOAD YET THIS |
| | IS ONLY SHOWN ON A SINGLE POLE 25AMP BRANCH CIRCUIT. |
| | PLEASE SEE 422.13, 240.4, 310.16 ETC |
| | |
| | 5) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE |
| | DETECTION DEVICES. |
| | PLEASE SEE THE PLANS CALL FOR *SMOKE DETECTORS* AND BY |
| | DEFINITION THIS WOULD MEAN THESE ARE PART OF A FIRE |
| | ALARM SYSTEM. SMOKE DETECTORS ONLY DETECT AND DO NOT |
| | SOUND WARNING. PLEASE SEE BASED ON PLANS AND PANEL |
| | SCHEDULE IT SEEMS THESE ARE *SMOKE ALARMS* WHICH |
| | ACTUALLY DETECT AND SOUND AND ALARM. |
| | PLEASE CLARIFY AND COMPLETE. |
| | |
| | 6) NOTE: PLEASE SEE 210.12 AS ARC FAULT PROTECTION IS |
| | REQUIRED FOR ALL BRANCH CIRCUITS/OUTLETS IN SLEEPING |
| | ROOMS. |
| | PLEASE SEE ONLY ONE BRANCH CIRCUIT FOR SMOKE DETECTION |
| | TYPE DEVICES SHOWS AFCI BREAKER. |
| | PLEASE ADJUST AND LIST ALL CIRCUITS REQUIRED. |
| | |
| | 7) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53 FOR |
| | SMALL APPLIANCE CIRCUITS ALONG WITH DINING AREAS AND |
| | AREAS OF THE LIKE. |
| | |
| | 8) NOTE: PLEASE CLARIFY IF THE PANEL SHOWN ON PLANS IS |
| | NEW OR ALREADY EXIST? SHOWN ON PLANS AS NEW YET NO |
| | CONDUCTORS FOR NEW OR EXISTING FEEDERS IS SHOWN. |
| | 240.4, 310.16 ETC |
| | |
| | 9) NOTE: PLEASE SEE NFPA-72 11.8.3 FOR SMOKE DETECTION |
| | DEVICE LOCATIONS. PLEASE SEE NO DEVICES SHALL BE WITHIN |
| | 3FT OF DOORS TO BATHROOMS. |
| | PLEASE SEE OTHER REQUIRED DISTANCES AND ALSO SPECIFIC |
| | REQUIREMENTS PER THE MANUFACTURE. |
| | 110.3 |
| | |
| | 10) NOTE: PLEASE SEE 210.11C3 FOR MISSING DEDICATED |
| | BATH CIRCUIT(S). |
| | MUST BE 20AMP AND #12. |
| | |
| | ** PLEASE COMPLETE THE ABOVE AND KNOW AS THERE IS |
| | INFORMATION NOT YET SHOWN A COMPLETE REVIEW FOR CODE |
| | COMPLIANCE CAN NOT BE DONE AT THIS TIME. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |