2007-11-19 12:51:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.A BLOCK SUBSTRATE REQUIRES USE OF THE CHART ON
 SHEET 8.
  
 2.SHUTTER CONNECTION MOUNTING TYPE IS TO CORRELATE
 WITH THE ANCHOR CHARTS ON SHEETS 7 AND 8 (IN THIS CASE,
 C1 THROUGH C5).
  
 PLEASE REVISE INSTALLATION SCHEDULE.
  
 NEW COMMENTS:
  
 3.ON THE INSTALLATION SCHEDULE, OPENINGS ARE NUMBERED
 1 OR 2, BUT SHOULD BE 1 THROUGH 26 TO CORRELATE WITH
 THE FLOOR PLAN.
  
 4.SEE SHEET 8.YOU'VE CIRCLED 6" ON THE CHART, C2
 CONNECTION TYPE, BUT THIS IS NOT THE ANCHOR SPACING
 YOU'VE SPECIFIED (7" AND 8", M/D CONNECTION TYPE).
  
 5.DPS ARE -145 ON THE INSTALLATION SCHEDULE.THIS
 SHUTTER DOES NOT COMPLY WITH THIS DESIGN PRESSURE, BUT
 WHY IS IT SO HIGH?
  
 PLEASE DO NOT RESUBMIT UNTIL YOU EITHER SPEAK WITH ME
 ON THE TELEPHONE OR SCHEDULE A MEETING TO DISCUSS.
  