| Plan Review Notes For Permit 07100292 |
| Permit Number |
07100292 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-11-19 12:51:42 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.A BLOCK SUBSTRATE REQUIRES USE OF THE CHART ON | | | SHEET 8. | | | | | | 2.SHUTTER CONNECTION MOUNTING TYPE IS TO CORRELATE | | | WITH THE ANCHOR CHARTS ON SHEETS 7 AND 8 (IN THIS CASE, | | | C1 THROUGH C5). | | | | | | PLEASE REVISE INSTALLATION SCHEDULE. | | | | | | NEW COMMENTS: | | | | | | 3.ON THE INSTALLATION SCHEDULE, OPENINGS ARE NUMBERED | | | 1 OR 2, BUT SHOULD BE 1 THROUGH 26 TO CORRELATE WITH | | | THE FLOOR PLAN. | | | | | | 4.SEE SHEET 8.YOU'VE CIRCLED 6" ON THE CHART, C2 | | | CONNECTION TYPE, BUT THIS IS NOT THE ANCHOR SPACING | | | YOU'VE SPECIFIED (7" AND 8", M/D CONNECTION TYPE). | | | | | | 5.DPS ARE -145 ON THE INSTALLATION SCHEDULE.THIS | | | SHUTTER DOES NOT COMPLY WITH THIS DESIGN PRESSURE, BUT | | | WHY IS IT SO HIGH? | | | | | | PLEASE DO NOT RESUBMIT UNTIL YOU EITHER SPEAK WITH ME | | | ON THE TELEPHONE OR SCHEDULE A MEETING TO DISCUSS. | | | |
|