| 2007-11-30 09:35:25 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS |
| | TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET 2 COMMERCIAL POOL RENOVATION, EXISTING WEST |
| | POOL PLAN PIPING: EXISTING GUTTER DRAINS INDICATE (16 |
| | PLACES), THE PLANS ARE INDICATING 12 GUTTER DRAINS. |
| | PLEASE CORRELATE THIS ON THE RESUBMITTAL. PER *106.1.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. SHEET A-2: THE RELOCATED DRAIN INLET INDICATED ON |
| | SHEET A-1 POOL DECK PLAN-DEMOLITION BY THE STEPS IS |
| | MISSING. PLEASE CLARIFY OR CORRECT THIS ON THE |
| | RESUBMITTAL. PER *106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 3. SHEET A-3: DELETE THE STUDOR VENT ON THE "CROSS |
| | SECTION THRU PLANTER W/NEW DRAIN SYSTEM". A STUDOR VENT |
| | IS NOT REQUIRED ON THE STORM DRAINAGE SYSTEM BECAUSE |
| | THERE ARE NO TRAPS ON THE SYSTEM. |
| | |
| | 4. SHEET A-3 "DECK DRAIN- CROSS SECTION" DETAIL: THE |
| | INDICATED TILE TECH PEDESTAL SYSTEM APPEARS TO OBSTRUCT |
| | THE DRAINAGE TO THE INDICATED DECK DRAINS BELOW THIS |
| | SYSTEM. PLEASE PROVIDE INFORMATION ON HOW THIS SYSTEM |
| | WILL WORK AND BE CODE COMPLIANT TO *1106.3 BUILDING |
| | STORM DRAINS AND SEWERS, AND PER *106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 5. SHEET A-2: PLEASE CLEARLY INDICATE WHICH DRAINS ARE |
| | LOCATED IN THE TILE TECH PEDESTAL SYSTEM ON THIS SHEET. |
| | PER *106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 6. DOES THIS EXISTING DECK HAVE ANY SECONDARY |
| | (EMERGENCY) DRAINAGE? WITH THE NEW ELEVATIONS OF THE |
| | DECK WITH THE INSTALLATION OF THE TILE TECH PEDESTAL |
| | SYSTEM DOES THIS EFFECT ANY EXISTING SECONDARY |
| | (EMERGENCY) DRAINAGE. PER *1107 SECONDARY (EMERGENCY) |
| | ROOF DRAINAGE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |