Plan Review Notes
Plan Review Notes For Permit 07100288
Permit Number 07100288
Review Stop P
Sequence Number 1
Notes
Date Text
2007-11-30 09:35:25PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 2 COMMERCIAL POOL RENOVATION, EXISTING WEST
 POOL PLAN PIPING: EXISTING GUTTER DRAINS INDICATE (16
 PLACES), THE PLANS ARE INDICATING 12 GUTTER DRAINS.
 PLEASE CORRELATE THIS ON THE RESUBMITTAL. PER *106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. SHEET A-2: THE RELOCATED DRAIN INLET INDICATED ON
 SHEET A-1 POOL DECK PLAN-DEMOLITION BY THE STEPS IS
 MISSING. PLEASE CLARIFY OR CORRECT THIS ON THE
 RESUBMITTAL. PER *106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. SHEET A-3: DELETE THE STUDOR VENT ON THE "CROSS
 SECTION THRU PLANTER W/NEW DRAIN SYSTEM". A STUDOR VENT
 IS NOT REQUIRED ON THE STORM DRAINAGE SYSTEM BECAUSE
 THERE ARE NO TRAPS ON THE SYSTEM.
  
 4. SHEET A-3 "DECK DRAIN- CROSS SECTION" DETAIL: THE
 INDICATED TILE TECH PEDESTAL SYSTEM APPEARS TO OBSTRUCT
 THE DRAINAGE TO THE INDICATED DECK DRAINS BELOW THIS
 SYSTEM. PLEASE PROVIDE INFORMATION ON HOW THIS SYSTEM
 WILL WORK AND BE CODE COMPLIANT TO *1106.3 BUILDING
 STORM DRAINS AND SEWERS, AND PER *106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 5. SHEET A-2: PLEASE CLEARLY INDICATE WHICH DRAINS ARE
 LOCATED IN THE TILE TECH PEDESTAL SYSTEM ON THIS SHEET.
 PER *106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 6. DOES THIS EXISTING DECK HAVE ANY SECONDARY
 (EMERGENCY) DRAINAGE? WITH THE NEW ELEVATIONS OF THE
 DECK WITH THE INSTALLATION OF THE TILE TECH PEDESTAL
 SYSTEM DOES THIS EFFECT ANY EXISTING SECONDARY
 (EMERGENCY) DRAINAGE. PER *1107 SECONDARY (EMERGENCY)
 ROOF DRAINAGE.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  