| Plan Review Notes For Permit 07100277 |
| Permit Number |
07100277 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-11-02 16:10:27 | BUILDING PROVISO: | | | TO BE IN PLACE AT C.O: | | | | | | PRIVATE | | | 1) 424.2.17.1 OUTDOOR SWIMMING POOLS. | | | OUTDOOR SWIMMING POOLS SHALL BE PROVIDED | | | WITH A BARRIER COMPLYING WITH | | | 424.2.17.1.1 THROUGH 424.2.17.1.14. | | | | | | 424.2.17.1.5 CHILD SAFETY BARRIER | | | ASTM D5034 100 LB TENSILE STRNGTH | | | ASTM D3787 150 LB BALL BURST | | | STRENGTH | | | 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED. | | | SPAS AND HEATED SWIMMING POOLS SHALL BE | | | EQUIPPED WITH A COVER DESIGNED TO | | | MINIMIZE HEAT LOSS. | | | | | | PUBLIC POOLS | | | 424.1.3.1.9 ALL PUBLIC POOLS SHALL BE SURROUNDED BY A | | | MINIMUM 48" IN HEIGHT FENCE. A SELF LATCHING SELF | | | CLOSING LOCKABLE GATE OF 48" MINIMUM HEIGHT WITH THE | | | LATCH LOCATED NEAR THE TOP. SAFETY COVERS THAT COMPLY | | | WITH ASTM F 1346 DO NOT SATIFY THIS REQUIREMENT. | | | | | | 13-412.1ABC2.6.2 POOL COVERS. HEATED POOLS SHALL BE | | | EQUIPPED WITH A VAPOR RETARDANT POOL COVER ON OR AT THE | | | WATER SURFACE. POOLS HEATED TO MORE THAN 90 DEGREES | | | (F) | | | SHALL HAVE A POOL COVER WITH A MINIMUM INSULATION VALUE | | | OF R-12. |
|