| | APPLICATION # 07100272 |
| | ELECTRICAL PLAN REVIEW |
| | 1020 PASEO ANDORRA |
| | 10/11/07 |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE |
| | NOTED. |
| | |
| | 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. A |
| | METER IS DRAWN ON THE RISER BUT A ?METER/MAIN? IS |
| | INDICATED. THERE IS NO EQUIPMENT GROUND TO THE PANEL |
| | SHOWN, IT IS UNCLEAR IF THE PANELIS PART OF THE |
| | ?METER/MAIN? OR STAND ALONE. |
| | |
| | 2} PROVIDE AN AIC RATING FOR THE NEW EQUIPMENT BEING |
| | INSTALLED PER 110.9 AND110.10. |
| | |
| | 3} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE |
| | EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS |
| | PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT |
| | TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS |
| | CHANGE. THE NOTES (11) REFERENCE 2002 NEC. |
| | |
| | 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER |
| | 106.1.3.FBC. |
| | |
| | 5} A RECEPTACLE NEEDS TO BE ADDED OR THE ONE SHOWN |
| | RELOCATED, TO COMPLY WITH 210.52(A)(1) IN THE ?PATIO, |
| | WHICH IS NOW A HABITABLE ROOM. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |