| Plan Review Notes For Permit 07100265 |
| Permit Number |
07100265 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-10-22 11:03:52 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | | ACCESS TO/EGRESS FROM THE OTHER TENANT SPACES ON THE | | | SAID FLOOR AND/OR THE BUILDING. | | | | | | 4.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE | | | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | 5.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 6.SPECIFY THE NEW WALL AND CEILING FINISH MATERIALS | | | IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|