2007-11-28 19:04:06PROJECT: 854 CONNISTON ROAD/# 07100262
  
 PROJECT SCOPE:
  
 CHANGE OF OCCUPANCY: CHURCH TO THEATER
 REMOVE CHURCH PEWS AND INSTALL NEW SEATING,FLOORING,
 THEATER CURTAINS.
  
 CODE REVIEW:
  
 2004 FLORIDA EXISTING BUILDING CODE W/2006 REVISIONS
 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS
 CITY OF WEST PALM BEACH ADMINISTRATION AMENDMENTS,
 CHAPTER 1, 2004 EDITION
  
 STATUS: FAILED
  
 COMMENTS:
  
 ****PLEASE REVISE PROJECT DETAIL ON THE PERMIT
 APPLICATION TO REFLECT ACTUAL WORK COMPLETED.*****
  
 1) PLEASE INDICATE THE LEVEL OF ALTERATION:
  
 301.5 . A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO SECTION
 303,304 & 305 OF THIS CODE.
  
 2)AS PER THE FBC 106.3.5, PLEASE PROVIDE THE
 FOLLOWING DATA:
  
 A) BUILDING CONSTRUCTION TYPE
 B) OCCUPANCY LOAD
 C) OCCUPANCY GROUP
 D) SPRINKLERED OR NON-SPRINKLERED.
  
 3) PLEASE SHOW THE DIMENSIONS OF THE BUILDING AND FLOOR
 AREA.
  
 4) PLEASE INDICATE THE SLOPE OF THE AISLES.
  
 5) PLEASE INDICATE THE CLEAR WIDTH DIMENSION OF THE
 AISLE ACCESSWAY:
  
 1024.10 AISLE ACCESSWAYS.
  
 THE AISLE ACCESSWAY BETWEEN ROWS OF SEATING SHALL HAVE
 A CLEAR WIDTH OF NOT LESS THAN 12 INCHES (305 MM), AND
 THE MINIMUM WIDTH SHALL BE INCREASED IN ACCORDANCE WITH
 SECTIONS 1024.10.2 FOR SEATING NOT AT TABLES AND
 SECTION 1024.10.2.2 FOR SEATING AT TABLES. THE WIDTH OF
 AISLE ACCESS-WAYS SHALL BE THE CLEAR HORIZONTAL
 DISTANCE FROM THE BACK OF THE ROW AHEAD AND THE NEAREST
 PROJECTION OF THE ROW BEHIND. WHERE CHAIRS HAVE
 AUTOMATIC OR SELF-RISING SEATS THAT COMPLY WITH ASTM F
 851, TEST METHOD FOR SELF-RISING SEAT MECHANISMS, THE
 MEASUREMENT SHALL BE MADE WITH SEATS IN THE RAISED
 POSITION. WHERE ANY CHAIR IN THE ROW DOES NOT HAVE AN
 AUTOMATIC OR SELF-RISING SEAT, THE MEASUREMENTS SHALL
 BE MADE WITH THE SEAT IN THE DOWN POSITION. FOR SEATS
 WITH FOLDING TABLET ARMS, ROW SPACING SHALL BE
 DETERMINED WITH THE TABLET IN THE USEABLE POSITION.
 EXCEPTION: WHEN NOT MORE THAN FOUR PERSONS ARE SERVED,
 THERE SHALL BE NO MINIMUM CLEAR WIDTH REQUIREMENT FOR
 THE PORTION OF THE AISLE ACCESSWAY HAVING A LENGTH NOT
 EXCEEDING 6 FEET (1.8 M) MEASURED FROM THE CENTER OF
 THE SEAT FARTHEST FROM THE AISLE.
  
 6) PLEASE INDICATE THE EGRESS TRAVEL DISTANCE TO THE
 EXIT DOORS, COMMON PATH OF TRAVEL,
 EXIT LIGHTS: PROVIDE LIFE SAFETY PLAN AS PER THE
 FOLLOWING:
  
 FLORIDA EXISTING BUILDING CODE
  
 812.4FIRE AND LIFE SAFETY.
 THE FIRE AND LIFE SAFETY PROVISIONS OF THIS SECTION
 SHALL BE APPLICABLE TO BUILDINGS OR PORTIONS OF
 BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION.
  
 7) PLEASE INDICATE THE ACCESSIBLE PARKING AND THE
 ACCESSIBLE ROUTE:
  
 806.1GENERAL.
 ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 8) PLEASE PROVIDE
 CLASSIFICATIONS/SPECIFICATIONS/TESTING RESULTS FOR THE
 WALL AND CEILLING INTERIOR FINISHES. ALL MATERIALS
 SHALL COMPLY WITH THE FOLLOWING:
  
 FLORIDA EXISTING BUILDING CODE
  
 812.3.1MINIMUM REQUIREMENTS.
 REGARDLESS OF T HE OCCUPANCY GROUP INVOLVED, THE
 FOLLOWING REQUIREMENTS SHALL BE MET:
 1. THE CAPACITY OF THE MEANS OF EGRESS SHALL
 COMPLY WITH FLORIDA BUILDING CODE, BUILDING.
 2. THE INTERIOR FINISH OF WALLS AND CEILINGS SHALL
 COMPLY WITH THE REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, BUILDING FOR THE NEW OCCUPANCY GROUP.
 3. COMPLIANCE WITH THE FLORIDA FIRE PREVENTION
 CODE.
  
 FLORIDA BUILDING CODE
  
 803.1 GENERAL.
  
 INTERIOR WALL AND CEILING FINISHES SHALL BE
 CLASSIFIED IN ACCORDANCE WITH ASTM E 84. SUCH INTERIOR
 FINISH MATERIALS SHALL BE GROUPED IN THE FOLLOWING
 CLASSES IN ACCORDANCE WITH
 THEIR FLAME SPREAD AND SMOKE-DEVELOPED INDEX.
  
 CLASS A:
 FLAME SPREAD INDEX 0-25; SMOKE-DEVELOPED INDEX
 0-450.
 CLASS B:
 FLAME SPREAD INDEX 26-75; SMOKE-DEVELOPED INDEX
 0-450.
 CLASS C:
 FLAME SPREAD INDEX 76-200; SMOKE-DEVELOPED INDEX
 0-450.
 EXCEPTION: MATERIALS, OTHER THAN TEXTILES, TESTED IN
 ACCORDANCE WITH SECTION 803.2.
 803.2INTERIOR WALL OR CEILING FINISHES OTHER THAN
 TEXTILES.
 INTERIOR WALL OR CEILING FINISHES, OTHER THAN
 TEXTILES, SHALL BE PERMITTED TO BE TESTED IN ACCORDANCE
 WITH NFPA 286. FINISHES TESTED IN ACCORDANCE WITH NFPA
 286 SHALL COMPLY
 WITH SECTION 803.2.1.
  
 9) THE PROJECT VALUATION APPEARS TO BE LOW. PLEASE
 PROVIDE DOCUMENTATION TO REFLECT THE ACTUAL REMODEL
 COST.
  
  
  
  