Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-11-29 13:39:38*****DENIED*****
  
 01.PROVIDE A SITE PLAN SHOWING RELATIONSHIP OF THE
 BUILDING TO STREETS, ROADS, ETC.
  
 02.PLANS HAVE NO POINT OF COMPASS.
  
 03.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 04.PLEASE LIST THE HAZARD OF CONTENTS OF THE
 STRUCTURE CLASSIFIED AS LOW, ORDINARY, OR HIGH.
  
 05.IS THE BUILDING FIRE SPRINKLERED AND DOES IT HAVE
 A FIRE ALARM SYSTEM.
  
 06.PROVIDE THE OCCUPANT LOAD, AS IN THE NUMBER OF
 PERSONS FOR WHOM MEANS OF EGRESS AND OTHER PROVISIONS
 ARE REQUIRED, THAT ARE CHARACTERISTIC OF THE USE OF THE
 SPACE OR SHALL BE DETERMINED AS THE MAXIMUM PROBABLE
 POPULATION OF THE SPACE UNDER CONSIDERATION, WHICHEVER
 IS GREATER.
  
 07.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN
 AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PROVIDED WITH PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH SHOWS
 TRAVEL DISTANCE TO THE EXITS.EXITS SHALL BE ARRANGED
 SO THAT THE TOTAL LENGHT OF TRAVEL FROM ANY POINT TO
 REACH AN EXIT SHALL NOT EXCEED 200 FEET OR 250 FEET IF
 THE OCCUPANCY HAS AN APPROVED SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM.
  
 09.SHOW LOCATION OF EXIT LIGHTS,EMERGENCY LIGHTS,
 AND FIRE EXTINGISHERS.
  
 10.PROVIDE INFORMATION ON THE TYPE OF COOKING
 EQUIPMENT TO BE USED IN THE CONCESSION AREA.
  
 11.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN THE CORRIDORS AND LOBBIES IN TERMS OF
 CLASS A, OR CLASS B.
  
 12.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIAL IN THE GENERAL ASSEMBLY AREA IN TERMS OF CLASS
 A, CLASS B, OR CLASS C.
  
 13.THEATER SCREENS ON WHICH PICTURES ARE PROJECTED
 SHALL BE CLASS A OR CLASS B.
  
 14.SPECIFY THE INTERIOR FLOOR FINISH IN EXIT
 ENCLOSURE, EXIT ACESS CORRIDORS AND IN OTHER SPACES AS
 CLASS I OR CLASS II.
  
 15.WORKSHOPS, STOREROOMS, PERMANENT DRESSING ROOMS,
 AND OTHER ACCESSORY SPACES CONTIGUOUS TO THE STAGE
 SHALL BE SEPARATED FROM EACH OTHER AND OTHER BUILDINGS
 BY AN 1-HOUR FIRE RESISTANCE-RATED CONSTRUCTION AND
 PROTECTED OPENINGS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW