| 2007-11-29 13:39:38 | *****DENIED***** |
| | |
| | 01.PROVIDE A SITE PLAN SHOWING RELATIONSHIP OF THE |
| | BUILDING TO STREETS, ROADS, ETC. |
| | |
| | 02.PLANS HAVE NO POINT OF COMPASS. |
| | |
| | 03.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 04.PLEASE LIST THE HAZARD OF CONTENTS OF THE |
| | STRUCTURE CLASSIFIED AS LOW, ORDINARY, OR HIGH. |
| | |
| | 05.IS THE BUILDING FIRE SPRINKLERED AND DOES IT HAVE |
| | A FIRE ALARM SYSTEM. |
| | |
| | 06.PROVIDE THE OCCUPANT LOAD, AS IN THE NUMBER OF |
| | PERSONS FOR WHOM MEANS OF EGRESS AND OTHER PROVISIONS |
| | ARE REQUIRED, THAT ARE CHARACTERISTIC OF THE USE OF THE |
| | SPACE OR SHALL BE DETERMINED AS THE MAXIMUM PROBABLE |
| | POPULATION OF THE SPACE UNDER CONSIDERATION, WHICHEVER |
| | IS GREATER. |
| | |
| | 07.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN |
| | AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS |
| | SHALL BE PROVIDED WITH PANIC HARDWARE OR FIRE EXIT |
| | HARDWARE. |
| | |
| | 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH SHOWS |
| | TRAVEL DISTANCE TO THE EXITS.EXITS SHALL BE ARRANGED |
| | SO THAT THE TOTAL LENGHT OF TRAVEL FROM ANY POINT TO |
| | REACH AN EXIT SHALL NOT EXCEED 200 FEET OR 250 FEET IF |
| | THE OCCUPANCY HAS AN APPROVED SUPERVISED AUTOMATIC |
| | SPRINKLER SYSTEM. |
| | |
| | 09.SHOW LOCATION OF EXIT LIGHTS,EMERGENCY LIGHTS, |
| | AND FIRE EXTINGISHERS. |
| | |
| | 10.PROVIDE INFORMATION ON THE TYPE OF COOKING |
| | EQUIPMENT TO BE USED IN THE CONCESSION AREA. |
| | |
| | 11.SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| | MATERIALS IN THE CORRIDORS AND LOBBIES IN TERMS OF |
| | CLASS A, OR CLASS B. |
| | |
| | 12.SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| | MATERIAL IN THE GENERAL ASSEMBLY AREA IN TERMS OF CLASS |
| | A, CLASS B, OR CLASS C. |
| | |
| | 13.THEATER SCREENS ON WHICH PICTURES ARE PROJECTED |
| | SHALL BE CLASS A OR CLASS B. |
| | |
| | 14.SPECIFY THE INTERIOR FLOOR FINISH IN EXIT |
| | ENCLOSURE, EXIT ACESS CORRIDORS AND IN OTHER SPACES AS |
| | CLASS I OR CLASS II. |
| | |
| | 15.WORKSHOPS, STOREROOMS, PERMANENT DRESSING ROOMS, |
| | AND OTHER ACCESSORY SPACES CONTIGUOUS TO THE STAGE |
| | SHALL BE SEPARATED FROM EACH OTHER AND OTHER BUILDINGS |
| | BY AN 1-HOUR FIRE RESISTANCE-RATED CONSTRUCTION AND |
| | PROTECTED OPENINGS. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | |