Date Text
2008-02-25 12:45:392004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) ONE WALL IS LESS THAN 6 FEET FROM THE PROPERTY LINE.
 IT IS NOTED FROM THE ARCHITECT'S RESPONSE THAT THE WALL
 HAS A ONE HOUR FIRE RATING. HOWEVER, NO OPENINGS ARE
 ALLOWED IN THIS WALL PER R302.2 OPENINGS. OPENINGS
 SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF A
 DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM
 AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET
 (1828 MM). THIS DISTANCE SHALL BE MEASURED
 PERPENDICULAR TO THE LINE USED TO DETERMINE THE
 SEPARATION DISTANCE. IF THERE ARE NO STRUCTURES LOCATED
 ON THE ADJACENT PROPERTY WITH WALLS WITHIN SIX FEET OF
 THE ADDITION, THEN COMPLIANCE WITH R302.1 AND R302.2
 HAS BEEN MEET. PROVIDE A SURVEY OR SITE PLAN INDICATING
 THE REQUIRED SEPARATION DISTANCE.
  
 4) SPECIFY THE SIZE OF THE ATTIC VENTS SPECIFIED ON
 A-2. SHOW COMPLIANCE WITH R806.2. THE TOTAL NET FREE
 VENTILATING AREA SHALL NOT BE LESS THAN 1 TO 150 OF THE
 AREA OF THE SPACE VENTILATED.
  
 5) THE 1X BUCKS SHOWN IN DETAILS ON S-1 ARE NOT DRAWN
 THE SAME WIDTH AS THE WINDOW AND DOOR FRAMES SUCH THAT
 FULL SUPPORT OF THE FRAMES IS PROVIDED. SEE FBC
 R613.6.1.1
  
 6) THE SIMPSON HTS CONNECTORS ARE SPECIFIED IN THE
 SCHEDULE ON S-2 WITH (20) - 10D X 1-1/2" FASTENERS. THE
 SIMPSON CATALOG REQUIRES (24) - 10D X 1-1/2" FASTENERS
 TO ACHIEVE THE 1450 UPLIFT. PLEASE CORRECT.
  
 7)SUBMIT PRODUCT APPROVALS FOR THE NEW FRONT AND SIDE
 METAL DOORS (#8 IN THE SCHEDULE ON A-1). FAC RULE
 9B-72. NOTE: PRODUCT APPROVALS ARE REQUIRED TO BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PER FBC 106.3* CITY AMENDMENTS.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE FLAT ROOF COVERING
 MATERIALS. SPECIFY THE APPROVED ASSEMBLY, FASTENING
 OPTION AND DESIGN PRESSURES. SUBMIT RAS 117
 CALCULATIONS FOR ENHANCED FASTENING.
  
 9) SUBMIT 2 COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY THE MOUNT TYPE,
 THE ANCHORS, ANCHOR SPACING, EDGE DISTANCE, GLASS
 SEPARATION DISTANCE, SPANS, ETC. SEE THE ATTACHED
 SAMPLE FORM.
  
 10)THE PRODUCT APPROVALS SUBMITTED FOR THE VINYL
 SOFFIT HAS DESIGN PRESSURES WHICH ARE TOO LOW. SEE FBC
 TABLE 1609.6C FOR COMPONENTS AND CLADDING AT
 OVERHANGS.
  
 11)THE WALL SECTION ON SHEET A-2 OF THE PLANS
 SPECIFIES A STUCCO SOFFIT. HOWEVER, PRODUCT APPROVALS
 WERE SUBMITTED FOR VINYL SOFFIT. PLEASE CLARIFY.
  
 12) IN ORDER TO EXPEDITE PLAN REVIEW, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE COMMENTS HAS
 BEEN ADDRESSED.
  