| Date |
Text |
| 2008-02-25 12:45:39 | 2004 FBC W/2007 REVISIONS |
| | ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) ONE WALL IS LESS THAN 6 FEET FROM THE PROPERTY LINE. |
| | IT IS NOTED FROM THE ARCHITECT'S RESPONSE THAT THE WALL |
| | HAS A ONE HOUR FIRE RATING. HOWEVER, NO OPENINGS ARE |
| | ALLOWED IN THIS WALL PER R302.2 OPENINGS. OPENINGS |
| | SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF A |
| | DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM |
| | AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET |
| | (1828 MM). THIS DISTANCE SHALL BE MEASURED |
| | PERPENDICULAR TO THE LINE USED TO DETERMINE THE |
| | SEPARATION DISTANCE. IF THERE ARE NO STRUCTURES LOCATED |
| | ON THE ADJACENT PROPERTY WITH WALLS WITHIN SIX FEET OF |
| | THE ADDITION, THEN COMPLIANCE WITH R302.1 AND R302.2 |
| | HAS BEEN MEET. PROVIDE A SURVEY OR SITE PLAN INDICATING |
| | THE REQUIRED SEPARATION DISTANCE. |
| | |
| | 4) SPECIFY THE SIZE OF THE ATTIC VENTS SPECIFIED ON |
| | A-2. SHOW COMPLIANCE WITH R806.2. THE TOTAL NET FREE |
| | VENTILATING AREA SHALL NOT BE LESS THAN 1 TO 150 OF THE |
| | AREA OF THE SPACE VENTILATED. |
| | |
| | 5) THE 1X BUCKS SHOWN IN DETAILS ON S-1 ARE NOT DRAWN |
| | THE SAME WIDTH AS THE WINDOW AND DOOR FRAMES SUCH THAT |
| | FULL SUPPORT OF THE FRAMES IS PROVIDED. SEE FBC |
| | R613.6.1.1 |
| | |
| | 6) THE SIMPSON HTS CONNECTORS ARE SPECIFIED IN THE |
| | SCHEDULE ON S-2 WITH (20) - 10D X 1-1/2" FASTENERS. THE |
| | SIMPSON CATALOG REQUIRES (24) - 10D X 1-1/2" FASTENERS |
| | TO ACHIEVE THE 1450 UPLIFT. PLEASE CORRECT. |
| | |
| | 7)SUBMIT PRODUCT APPROVALS FOR THE NEW FRONT AND SIDE |
| | METAL DOORS (#8 IN THE SCHEDULE ON A-1). FAC RULE |
| | 9B-72. NOTE: PRODUCT APPROVALS ARE REQUIRED TO BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PER FBC 106.3* CITY AMENDMENTS. |
| | |
| | 8) SUBMIT PRODUCT APPROVALS FOR THE FLAT ROOF COVERING |
| | MATERIALS. SPECIFY THE APPROVED ASSEMBLY, FASTENING |
| | OPTION AND DESIGN PRESSURES. SUBMIT RAS 117 |
| | CALCULATIONS FOR ENHANCED FASTENING. |
| | |
| | 9) SUBMIT 2 COPIES OF A KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS. SPECIFY THE MOUNT TYPE, |
| | THE ANCHORS, ANCHOR SPACING, EDGE DISTANCE, GLASS |
| | SEPARATION DISTANCE, SPANS, ETC. SEE THE ATTACHED |
| | SAMPLE FORM. |
| | |
| | 10)THE PRODUCT APPROVALS SUBMITTED FOR THE VINYL |
| | SOFFIT HAS DESIGN PRESSURES WHICH ARE TOO LOW. SEE FBC |
| | TABLE 1609.6C FOR COMPONENTS AND CLADDING AT |
| | OVERHANGS. |
| | |
| | 11)THE WALL SECTION ON SHEET A-2 OF THE PLANS |
| | SPECIFIES A STUCCO SOFFIT. HOWEVER, PRODUCT APPROVALS |
| | WERE SUBMITTED FOR VINYL SOFFIT. PLEASE CLARIFY. |
| | |
| | 12) IN ORDER TO EXPEDITE PLAN REVIEW, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE COMMENTS HAS |
| | BEEN ADDRESSED. |
| | |