| 2008-01-17 16:35:46 | 2004 FBC W/2007 REVISIONS |
| | ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) ONE WALL OF THE ADDITION IS LESS THAN 6 FEET FROM |
| | THE PROPERTY LINE. SHOW COMPLIANCE WITH R302.1 EXTERIOR |
| | WALLS. |
| | EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) |
| | SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE |
| | RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL |
| | NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM |
| | AN ADJACENT PROJECTION OR WALL. |
| | |
| | 4) SHOW COMPLIANCE WITH R806.1 AND R806.2 FOR ROOF |
| | VENTILATION. |
| | |
| | 5) SHOW COMPLIANCE WITH R403.1.4 MINIMUM DEPTH. ALL |
| | EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 INCHES |
| | (305 MM) BELOW THE UNDISTURBED GROUND SURFACE. |
| | |
| | 6) SHOW COMPLIANCE WITH R319.1 LOCATION REQUIRED. IN |
| | AREAS SUBJECT TO DECAY DAMAGE AS ESTABLISHED BY TABLE |
| | R301.2(1) , THE FOLLOWING LOCATIONS SHALL REQUIRE THE |
| | USE OF AN APPROVED SPECIES AND GRADE OF LUMBER, |
| | PRESSURE TREATED IN ACCORDANCE WITH AWPA C1, C2, C3, |
| | C4, C9, C15, C18, C22, C23, C24, C28, C31, C33, P1, P2 |
| | AND P3, OR DECAY-RESISTANT HEARTWOOD OF REDWOOD, BLACK |
| | LOCUST, OR CEDARS. 5. WOOD SIDING, SHEATHING AND WALL |
| | FRAMING ON THE EXTERIOR OF A BUILDING HAVING A |
| | CLEARANCE OF LESS THAN 6 INCHES (152 MM) FROM THE |
| | GROUND. |
| | |
| | 7) SHOW COMPLIANCE WITH SECTION 704 |
| | INSPECTION FOR TERMITES |
| | IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE |
| | INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS |
| | AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING |
| | SHALL NOT BE LESS THAN 6 INCHES (152 MM). EXCEPTIONS: |
| | 1.PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS |
| | THAN 5 / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE |
| | MASONRY FOUNDATION SIDEWALL. |
| | 2.ACCESS OR VEHICLE RAMPS WHICH RISE TO THE |
| | INTERIOR FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH |
| | RAMPS ONLY. |
| | 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO |
| | AND GARAGE SLABS AND ENTRY AREAS. |
| | 4.IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES, |
| | THE FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR |
| | FINISH FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY. |
| | 5.MASONRY VENEERS. |
| | |
| | 8) SPECIFY THE SOFFIT COVERING MATERIAL ON THE PLANS. |
| | IF IT IS VINYL OR ALUMINUM, SUBMIT PRODUCT APPROVALS |
| | WITH ADEQUATE DESIGN PRESSURES. FBC 106.1.2 CITY |
| | AMENDMENTS |
| | |
| | 9) R613.6.1.1 UNLESS OTHERWISE TESTED, BUCKS SHALL |
| | EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW OR DOOR |
| | FRAME SUCH THAT FULL SUPPORT OF THE FRAME IS PROVIDED. |
| | THE WINDOW AND EXTERIOR JAMB DETAILS ON S-1 DO NOT SHOW |
| | THE BUCKS FULLY SUPPORTING THE WINDOW AND DOOR FRAMES. |
| | PLEASE CORRECT. |
| | |
| | 10) THE HTS CONNECTORS ON SHEET S-2OF THE SIMPSON |
| | CONNECTOR SCHEDULE HAS THE WRONG NUMBER OF FASTENERS |
| | SPECIFIED. THE SIMPSON CATALOG SPECIFIES 24- 10D X |
| | 1-1/2" NAILS OR 20- 10D NAILS TO ACHIEVE THE 1450 |
| | UPLIFT. PLEASE CORRECT. |
| | |
| | 11) NOTE: SOME OF THE UPLIFTS SPECIFIED FOR THE TRUSSES |
| | ON THE ROOF FRAMING PLAN ON SHEET S-2 ARE LESS THAN |
| | SPECIFIED ON THE TRUSS DRAWINGS, HOWEVER, THE SPECIFIED |
| | CONNECTORS ARE ADEQUATE. |
| | |
| | 12)THE NEW TRUSS LAYOUT IS REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| | THE PROJECT. FBC R106.1.3. |
| | |
| | 13) SHOW COMPLIANCE WITH R308.4 FOR SAFETY GLAZING IN |
| | THE BATHROOM WINDOW. |
| | |
| | 14)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. |
| | THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 15) SUBMIT PRODUCT APPROVALS FOR THE SINGLE OUTSWING |
| | FRONT AND SIDE DOORS ( NUMBER 8 ON THE DOOR SCHEDULE). |
| | FAC RULE 9B-72. |
| | |
| | 16) THE PRODUCT APPROVALS SUBMITTED FOR THE TRACO |
| | SINGLE HUNG WINDOWS ARE EXPIRED (SEE NOA |
| | NO.05-0729.03).PLEASE SUBMIT CURRENT PRODUCT |
| | APPROVALS AS REQUIRED BY FAC RULE 9B-72. |
| | |
| | 17) SUBMIT PRODUCT APPROVALS FOR THE FLAT AND SLOPE |
| | ROOF COVERING MATERIALS ( APPROVED IN WRITING BY THE |
| | DESIGNER) . SPECIFY THE APPROVED ASSEMBLY, FASTENING |
| | OPTION AND DESIGN PRESSURE FOR THE FLAT ROOF WITH RAS |
| | 117 CALCULATIONS FOR ENHANCED FASTENING. |
| | |
| | 18) SUBMIT 2 COPIES OF A KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS. SPECIFY THE MOUNT TYPE, |
| | THE ANCHORS, THE ANCHOR SPACING, THE EDGE DISTANCE, |
| | GLASS SEPARATION, SPANS, ETC. SEE ATTACHED SAMPLE. |
| | |
| | 19) SHOW COMPLIANCE WITH R310.4 THE TEMPORARY |
| | INSTALLATION OR CLOSURE OF STORM SHUTTERS, PANELS, AND |
| | OTHER APPROVED HURRICANE PROTECTION DEVICES SHALL BE |
| | PERMITTED ON EMERGENCY ESCAPE AND RESCUE OPENINGS |
| | DURING THE THREAT OF A STORM. SUCH DEVICES SHALL NOT BE |
| | REQUIRED TO COMPLY WITH THE OPERATIONAL CONSTRAINTS OF |
| | SECTION R310.1.4 . WHILE SUCH PROTECTION IS PROVIDED, |
| | AT LEAST ONE MEANS OF ESCAPE FROM THE DWELLING OR |
| | DWELLING UNIT SHALL BE PROVIDED. THE MEANS OF ESCAPE |
| | SHALL BE WITHIN THE FIRST FLOOR OF THE DWELLING OR |
| | DWELLING UNIT AND SHALL NOT BE LOCATED WITHIN A GARAGE |
| | WITHOUT A SIDE HINGED DOOR LEADING DIRECTLY TO THE |
| | EXTERIOR. OCCUPANTS IN ANY PART OF THE DWELLING OR |
| | DWELLING UNIT SHALL BE ABLE TO ACCESS THE MEANS OF |
| | ESCAPE WITHOUT PASSING THROUGH A LOCKABLE DOOR NOT |
| | UNDER THEIR CONTROL. |
| | |
| | 20) SHEET CVR-1 SPECIFIES REFERENCES FROM FBC |
| | RESIDENTIAL CHAPTER 44 WHICH APPLIES TO THE |
| | HIGH-VELOCITY HURRICANE ZONE. THEY DO NOT APPLY TO THE |
| | CITY OF WEST PALM BEACH, WHICH IS NOT LOCATED IN THIS |
| | ZONE. PLEASE CORRECT. |
| | THERE ARE FEES THAT ARE OWED ON THIS PERMIT WHICH MUST |
| | BE PAID BEFORE THE PLANS CAN BE PICKED UP. |
| | |
| | 21) IN ORDER TO EXPEDITE PLAN REVIEW, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE COMMENTS HAS |
| | BEEN ADDRESSED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |