| Plan Review Notes For Permit 07100254 |
| Permit Number |
07100254 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-25 13:21:52 | DENIED; | | | 1. FLOOR PLANS ON A-1 DO NOT MATCH. ELECTRICAL PLAN | | | SHOWS WATER HEATER IN A DIFFERENT LOCATION THAN FLOOR | | | PLAN. THIS WILL MAKE A DIFFERANCE WHEN ROUGHING IN THE | | | ELECTRIC AND PLUMBING. | | | 2. THE AUTOMATIC CLOTHES WASHER DISCHARGE IS NOT | | | PERMITED TO RUN THRU A BATHROOM GROUP. SEE FBC-PLUMBING | | | SECTION 909.1. | | | 3. W/M BRANCH DRAIN TO BE 3" TO THE WASTE ARM SECTION | | | 406.3. A CLEANOUT TO BE INSTALLED AT 48" OFF FINISH | | | FLOOR. | | | 4. SIZE ALL PIPES ON RISER DIAGRAM. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|