Plan Review Notes
Plan Review Notes For Permit 07100254
Permit Number 07100254
Review Stop P
Sequence Number 1
Notes
Date Text
2007-10-25 13:21:52DENIED;
 1. FLOOR PLANS ON A-1 DO NOT MATCH. ELECTRICAL PLAN
 SHOWS WATER HEATER IN A DIFFERENT LOCATION THAN FLOOR
 PLAN. THIS WILL MAKE A DIFFERANCE WHEN ROUGHING IN THE
 ELECTRIC AND PLUMBING.
 2. THE AUTOMATIC CLOTHES WASHER DISCHARGE IS NOT
 PERMITED TO RUN THRU A BATHROOM GROUP. SEE FBC-PLUMBING
 SECTION 909.1.
 3. W/M BRANCH DRAIN TO BE 3" TO THE WASTE ARM SECTION
 406.3. A CLEANOUT TO BE INSTALLED AT 48" OFF FINISH
 FLOOR.
 4. SIZE ALL PIPES ON RISER DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695