Plan Review Notes
Plan Review Notes For Permit 07100254
Permit Number 07100254
Review Stop M
Sequence Number 1
Notes
Date Text
2007-10-16 11:51:31PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) MECHANICAL PLAN PAGE M-1. THE SITTING ROOM WILL
 REQUIRE RETURN AIR, SEE 2004 FBC/R M1602.4.
  
 2) MECHANICAL PLAN PAGE M-1. THE ARCHITECT NEEDS TO
 SHOW THE DATE WERE HE SIGNED AND SEALED THE PLAN, SEE
 FAC 61G1-16.004 (5).
  
 3) MECHANICAL PLAN PAGE M-1. EQUIPMENT SCHEDULE SHOWS
 FUSE SIZE FOR AHU TO BE 45 AMP, ELECTRICAL PLAN SHOWS
 50 AMP, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]