| Plan Review Notes For Permit 07100254 |
| Permit Number |
07100254 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-16 11:51:31 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) MECHANICAL PLAN PAGE M-1. THE SITTING ROOM WILL | | | REQUIRE RETURN AIR, SEE 2004 FBC/R M1602.4. | | | | | | 2) MECHANICAL PLAN PAGE M-1. THE ARCHITECT NEEDS TO | | | SHOW THE DATE WERE HE SIGNED AND SEALED THE PLAN, SEE | | | FAC 61G1-16.004 (5). | | | | | | 3) MECHANICAL PLAN PAGE M-1. EQUIPMENT SCHEDULE SHOWS | | | FUSE SIZE FOR AHU TO BE 45 AMP, ELECTRICAL PLAN SHOWS | | | 50 AMP, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|