 APPLICATION #07100254
 ELECTRICAL PLAN REVIEW
 623 47TH STREET
 10/12/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET A-1, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 1} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 2} THE 50 AMP OCP FOR THE AHU IN THE PANEL DOES NOT
 CORRELATE WITH THE MAXIMUM FUSE SIZE GIVEN FOR THAT
 UNIT ON SHEET M-1, 45 AMPS.
  
 3} THE PANEL LOCATION IS IN VIOLATION OF 110.26
 CLEARANCE REQUIREMENTS (3?), WITH REGARD TO THE WASHER
 AND POSSIBLY THE WATER HEATER.
  
 4} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED
 PER 230.70, 225.32. INDICATE LOCATION ON PLAN PER
 230.72(A)(1). THE PANEL IS LISTED AS MLO. THE AHJ HAS
 DETERMINED THAT ?NEAREST POINT OF ENTRANCE? SHALL BE NO
 FARTHER THAN 8? OF UNPROTECTED CONDUCTORS.
  
 5} THE APPLICATION INDICATES A DINING ROOM IS TO BE
 ADDED, THAT ROOM IS NOT SHOWN ON THE FLOOR PLAN AND
 WOULD BE SUBJECT TO 210.52(B)(1), SMALL APPLIANCE
 CIRCUIT. CORRELATE THE SCOPE ON THE APPLICATION WITH
 THE PLANS, 106.1.1 FBC AS AMENDED.
  
 6} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. THIS
 INCLUDES THE COUNTER BETWEEN THE RANGE AND
 REFRIGERATOR.
  
 7} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), THERE IS NO BATH CIRCUIT LISTED ON
 THE PANEL SCHEDULE.
  
 8} A RECEPTACLE PER 210.63 IS REQUIRED FOR THE A/C
 CONDENSER.
  
 9} THE LOCATION SHOWN FOR THE DISCONNECTING MEANS FOR
 THE CONDENSER IS IN VIOLATION OF 110.26.
  
 10} THE STATE OF FLORIDA PER 553 FS HAS ADOPTED THE
 2004 FBC AND ALL REFERENCED MATERIAL. PLEASE CHANGE ALL
 NOTES TO REFLECT THIS CHANGE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  