2008-07-15 12:15:12PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE LETTER FROM THE ENGINEER NEEDS TO BE THE
 ORIGINAL WITH THE RAISED SEAL AND SIGNATURE, NOT A COPY
 PER 2004 FAC 61G15-23.002. PLEASE HAVE THE PERMIT
 NUMBER MENTIONED IN THE LETTER ALSO.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 3) PLEASE SUBMIT TWO COPIES OF THE ENERGY CALCULATIONS,
 AS ONLY ONE WAS SUBMITTED.
  
 4) THE ENGINEER'S NAME AND INFORMATION MUST NOT APPEAR
 ON THE REVISED PLANS AS HE IS REMOVING HIMSELF FROM THE
 PROJECT.
  
 5) SHOW THE LOCATION OF THE A/C CONDENSER UNITS ON THE
 REVISED MECHANICAL PLAN, PER 2004 FBC/R M1307.
  
 6) SHOW THE SIZE OR THE RETURN AIR TRANSFER DUCTS
 (FLEX) TO THE MUDROOM (SEE YELLOW HIGH LIGHT ON PAGE 1)
 PER 2004 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]