Plan Review Notes
Plan Review Notes For Permit 07100247
Permit Number 07100247
Review Stop B
Sequence Number 2
Notes
Date Text
2008-01-02 17:02:01RESIDENTIAL ADDITION, BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-SECOND FLOOR PLAN SPECIFIES THEGUEST BEDROOM
 CENTER WINDOW AS THE EGRESS WINDOW,WHILE EXTERIOR
 SOUTH ELEVATION SPECIFIES THE SIDE WINDOWS AS THE
 EGRESS WINDOWS.CLARIFY WHICH ONE IS THE EGRESS
 WINDOW.
  
 2- PROVIDE COMPLETE SPECIFICATIONS/DETAILS FOR
 FIREBLOCKING IN THE WALL SECTIONS.FIREBLOCKING IS NOT
 ONLY REQUIRED BETWEEN FIRST AND SECOND FLOOR, BUT
 BETWEEN TOP WALL AND CEILING AS WELL. SEC. R602..1.2 OF
 2004 FLORIDA RESIDENTIAL CODE.PROVIDE INFORMATION AS
 REQUIRED. (REPEAT COMMENT. COMMENT PARTIALLY
 ADDRESSED).
  
 3-SPECIFY CEILING FAN SIZES IN ALL ROOMS AS REQUIRED
 BY TABLE 13-607.1.A.1 FBC 2004 SINCE ENERGY
 CALCULATIONS ARE TAKEN THE CEILING FANS CREDIT. (REPEAT
 COMMENT).
  
 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) OPERABLEWINDOWS FOR DOUBLE AND SINGLE CASEMENT
 WINDOWS AS SHOWN ON PLANS.PRODUCT APPROVALNOA
 07-0524.06 SUBMITTED DOESN'T COVER THESE WINDOWS.
 B) EXTERIORSWING DOOR AT MUD ROOM AS SHOWN ON
 EXTERIOR SOUTH ELEVATION. ONLY PRODUCT APPROVAL FOR
 FRENCH DOORS WAS SUBMITTED.
 C) ALL SIMPSON STRUCTURAL CONNECTORS. PROVIDE 2
 COPIES ONLY ONE WAS SUBMITTED.
  
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.THERE ARE SOME PRODUCT
 APPROVALS WHICH ONLYONE COPY WAS SIGNED OFF AS
 REVIEWED AND APPROVED.PLEASE RESUBMIT COMPLETE
 PRODUCT APPROVALS PACKAGE.ALSO,WRITE THE NAME OF
 ARCHITECT REVIEWING THE PRODUCT APPROVAL. SEC. 106..3.3
 CITY AMENDMENTS TO FBC 2004.
  
 6- REVISED PLANS SPECIFY ICYNENE INSULATION NOW.
 PROVIDE COMPLETELISTING AND MANUFACTURER'S SPECS TO
 VERIFY COMPLIANCE WITHSECTION R314 OF 2004 FLORIDA
 RESIDENTIAL CODE. AND TO VERIFY COMPLIANCE WITH
 SPECIFIED R-VALUE OF R-30. ALSO, ARCHITECT TO
 COORDINATE WITH ENERGY CALCULATIONS PRIOR TO
 SUBMITTAL.
  
 7-SHEET 7:REVISE EMBEDMENT SPECIFIED FOR 5" ANCHOR
 BOLTS THRU 3X8 LEDGER.IT CAN'T BE 3 1/2" EMBEDMENT.
  
 8-SHEET 8: REVISE HEADROOM CLEARANCE IN SECTION 1/8.
 SEE SEC.R311.5.2 OF 2004 FLORIDA RESIDENTIAL CODE TO
 CHECK PROPER WAY OF PROVIDING DIMENSION.ANDPROVIDE
 DIMENSION INFEET AND INCHES.
  
 9- SHEET 10: REVISE DESIGN DATA NOTE #2. SEE SEC.
 R606.4 FOR MINIMUM COMPRESSIVE STRESS REQUIRED FOR
 CONCRETE BLOCK.(REPEAT COMMENT).ENGINEER CAN'T
 LOWER THE MINIMUMCOMPRESSIVE STRESS REQUIRED BY THE
 CODE. REVISE AS REQUIRED.
  
 10- NOTICE OF COMMENCEMENT WAS NOT SUBMITTED THIS TIME.
 THIS LEGAL DOCUMENT NEEDS TO BE SIGNED BY THE OWNER.
 OTHERWISE, PROVIDE LEGAL DOCUMENTATION AND FLORIDA
 STATUTE SECTIONTHAT ALLOWS THE CONTRACTOR TO SIGN IT
 ON BEHALF OF THE OWNER.
  
 11- PERMIT APPLICATION IS MISSING THE SECOND PAGE.
 PROVIDECOMPLETE PERMIT APPLICATION.
  
 12-PERMIT VALUATION WAS UPDATED ONCE THAT AREA
 TABULATION WAS PROVIDED IN THE PLANS. OWES $934.73 FOR
 PERMIT VALUATION AND RADON FEES AS REQUIRED BY SEC.
 108.3 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712