Plan Review Notes
Plan Review Notes For Permit 07100247
Permit Number 07100247
Review Stop P
Sequence Number 1
Notes
Date Text
2007-10-29 07:37:43DENIED;
 1. SHOW LOCATION, SIZE AND TYPE, OF ENERGY USED, WATER
 HEATER.
 2. KITCHEN SINK MISSING FROM SANITARY RISER DIAGRAM.
 3. AUTOMATIC CLOTHES WASHERS BRANCH DRAINS SHALL BE 3"
 SEE FBC PLUMBING SECTION 406.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695