| 2007-10-16 13:41:30 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE ON FORM600A-04R, | | | SEE 2004 FBC 13-600.3.A (12-8-06 REVISION). | | | | | | 2) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004 | | | FBC 13-607.1.ABC.1. | | | | | | 3) SHOW THE LOCATION OF THE CONDENSER UNITS ON THE | | | MECHANICAL PLANS. | | | | | | 4) SHOW THE BATHROOM EXHAUST FANS AND CFM'S. ON THE | | | MECHANICAL PLANS, SEE 2004 FBC/R 303.3 EXCEPT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|