| 2007-10-12 14:21:44 | |
| | |
| | APPLICATION #07100247 |
| | ELECTRICAL PLAN REVIEW |
| | 165 ELWA PL |
| | 10/12/07 |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | ALL COMMENTS RELATE TO SHEET 11, UNLESS OTHERWISE |
| | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| | OTHERWISE NOTED. |
| | |
| | 1} 230.2 ALLOWS ONLY ONE SERVICE TO A BUILDING. |
| | INDICATE WHICH EXCEPTION, IF ANY, ALLOWS TWO SERVICES |
| | TO THIS RESIDENCE. |
| | |
| | 2} THERE IS NO GROUNDING ELECTRODE CONDUCTOR SHOWN FOR |
| | THE SECOND SERVICE IF ALLOWED. 250.66. |
| | |
| | 3} IF ALLOWED, THE SECOND DISCONNECTING MEANS MUST |
| | COMPLY WITH 110.9 AND 110.10: OBTAIN THE AVAILABLE |
| | FAULT CURRENT AT THE UTILITY AND CALCULATE THE SAME AT |
| | THE EQUIPMENT. INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN THE AVAILABLE |
| | FAULT. |
| | |
| | 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. THE |
| | COUNTERTOP SPACING DOES NOT COMPLY. |
| | |
| | 5} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. |
| | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| | 440.14, RECEPTACLE PER 210.63. |
| | |
| | 6} SHEET #12. THE RECEPTACLE SPACING IN THE GUEST BATH |
| | MUST MEET 210.52(D). ONE NEEDS TO BE ADDED OR |
| | RELOCATED. |
| | |
| | 7} THERE IS A NOTE REGARDING A PUMP RECEPTACLE. IF FOR |
| | A WHIRLPOOL OR JACUZZI, THERE IS NONE LISTED ON THE |
| | SCHEDULES. ALSO SEE 210.23(A)(2) FOR LOADING ON THE |
| | BATH CIRCUIT. |
| | |
| | 8} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. THERE IS |
| | NONE SHOWN ON THE FIRST FLOOR AT THE STAIR. THIS |
| | APPLIES TO THE ALARMS IN THE ENTIRE RESIDENCE AS IT IS |
| | A SINGLE FAMILY DWELLING. A NOTE ALONG THOSE LINES, |
| | ALTHOUGH NOT AN ISSUE WITH THE NEC, ZONING MAY NOT |
| | ALLOW A SECOND KITCHEN IN A SINGLE FAMILY RESIDENCE. |
| | |
| | 9} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| | DESIGNED. |
| | |
| | PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH |
| | CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM |
| | SEPARATELY TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | ANSWER REVIEW COMMENTS IN WRITING. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |