2007-11-06 15:46:44RESIDENTIAL ADDITION BUILDING REVIEW CHECKLIST. REVIEW
 UNDER EXISTING BUILDING CODE 2004,FLORIDA RESIDENTIAL
 CODE 2004 AND FBC 2004 WITH 2007 REVISIONS.
  
 1- BRING PLANS TO PALM BEACH COUNTYAT 2300 N. JOG RD.
 TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 2- NOTICE OF COMMENCEMENT WAS SIGNEDBY THE
 CONTRACTOR. THIS SPACE IS TO BE SIGNED BY THE OWNER.
 OTHERWISE PROVIDE LEGAL DOCUMENTATION SHOWING THE
 CONTRACTOR AS THE OWNER'S AUTHORIZED
 OFFICER/DIRECTOR/PARTNER/MANAGER. PROVIDE REVISED AND
 RE-RECORDED NOTICE OF COMMENCEMENT AS REQUIRED.
  
 3- PLANS TO SPECIFY AREA TABULATION, INCLUDING THE
 LOGGIA AREA TO PROPERLY EVALUATE THE BUILDING PERMIT
 VALUE AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC
 2004.
  
 4- NORTH WALL OF PROPOSED ADDITION IS LESS THAN 6'-0"
 FROM THE PROPERTY LINE, THEREFORE NEED TO SPECIFY ONE
 HOUR FIRE RATED WALL(FROM INSIDE AND OUTSIDE) AS
 REQUIRED BY SEC. R302.1 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 5- OPENINGS IN NORTH WALL ARE NOT ALLOWED AS REQUIRED
 BY SEC. R302.2 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 6- PROVIDE SPECIFICATIONS FOR GARAGE DOOR LEADING TO
 THE MUD ROOM TO COMPLY WITHSEC. R309.1 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 7- REVISE ROOF SHEATHING FASTENING SPACING FOR FLAT
 ROOF AT ZONE 3AND SECOND FLOOR ROOF AT ZONE 3
 SHEATHING AS REQUIRED BY SEC. R803.2.3.1 OF 2004
 FLORIDA RESIDENTIAL CODE.NAILS TO BE 4"O.C.
 MINIMUM.
  
 8- PROVIDE COMPLETESPECIFICATIONS FOR NAILING OF 2X6
 TONGUE AND GROVE ROOF SHEATHING IN LOGGIA ROOF TO
 VERIFY COMPLIANCEWITH CALCULATED UPLIFT LOADS.SEC.
 R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 9- ARCHITECTURAL PLANS NEED TO SPECIFY TYPE OF WINDOWS
 AND SIZES.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO
 VERIFY COMPLIANCE WITH EGRESS REQUIREMENTS AND ENERGY
 CALCULATIONS AS REQUIRED CHAPTER 13 OF FBC 2004.
  
 10- SPECIFY ATTIC ACCESS SIZE AND LOCATION AS REQUIRED
 BY SEC. R807 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 11- PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR
 FIREBLOCKING SHOWING COMPLIANCE WITH SEC. R602.1.2 AND
 SEC. R602.1.2.1 OF 2004 FLORIDA RESIDENTIAL CODE.
 PROVIDE INFORMATION IN ALL WALL SECTIONS AND STAIRS.
  
 12- ENERGY CALCULATIONS:
 A) NEED TO COMPLETE REVISED FORM 600A-2004R.
  
 B) COMPLETE ALL INFORMATION ON TOP OF FORM.
  
 C) REVISE OVERHANG LENGTH AND OVERHANG HEIGHT.IT
 CAN'T BE ZERO. SEE PLANS AND REVISE AS REQUIRED. SEE
 SEC. R601.1.ABC.3 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 D) ENGINEER WHO PREPARED THE ENERGY CALCULATIONS
 NEED TO PROVIDEALL HIS INFORMATION AS REQUIRED BY
 SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 E) ARCHITECT TO PROVIDE HIS INFORMATION AND SEAL AS
 REQUIRED BY SEC. 61G1-16.003 OF FLORIDA ADMINISTRATIVE
 CODE.
  
 13- IF ENERGY CALCULATIONS ARE TAKING THE CEILING FAN
 CREDIT, THEN DRAWINGS NEED TO SHOW CEILING FAN SIZE IN
 ALL ROOMS. SEE TABLE 13-607.1.A.1 FBC 2004 FOR MINIMUM
 SIZE OF CEILING FAN REQUIRED.
  
 14- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 ***ONLY PRODUCT APPROVAL FOR ROOF TILE AND ROOF TILE
 ADHESIVE WAS SUBMITTED.
  
 A) ALL FIXED AND OPERABLE WINDOWS AS SHOWN ON
 PLANS.
  
 B) ALL EXTERIOR DOORS AS SHOWN ON PLANS. FRENCH
 DOORS AND SWING DOOR AT MUD ROOM.
  
 C) WINDOW MULLIONS.
  
 D) FLAT ROOF.AND PROVIDE THE FOLLOWING
 INFORMATION:
 * IDENTIFY SPECIFIC ASSEMBLY TO BE INSTALLED.
 ** CHECK IF SELECTED ASSEMBLY IS LIMTED BY GENERAL
 LIMITATION #7 OR #9. IF LIMITED BY GENERAL LIMITATION
 #9, THEN IT CAN'T BE USED IN THIS AREA. IF LIMITED BY
 GENERAL LIMTATION #7, THEN PROVIDE THE RAS 117
 CALCULATIONS TO ENHANCE NAIL FASTENING AT PERIMETER AND
 CORNER AREAS. SEE GENERAL LIMITATION #7. IF
 CALCULATIONS ARE REQUIRED TO BE BY ARCHITECT, ENGINEER
 OR REGISTERED ROOF CONSULTANT, THEN ONLY ONE OF THOSE
 PROFESSIONALS CAN PROVIDE THE CALCULATIONS.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS. PROVIDE PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIC CONNECTOR ONLY.
  
 F) PRECAST CONCRETE LINTELS.
  
 G) STORM SHUTTERS IF WINDOWS AND DOORS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 16- SPECIFY ROOF CROSS VENTILATION FOR FLAT AND PITCHED
 ROOFS AS REQUIRED BYSEC. R806 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 17- WINDOWS NEXT TO FRENCH DOORS IN FAMILY AREA AND
 WINDOW NEXT TO THE BATH TUB IN SECOND FLOOR REQUIRE
 SAFETY GLASS AS REQUIRED BY SEC. R308.4 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 18- SPECIFY FLAT ROOF SLOPE TO VERIFY COMPLIANCE WITH
 SEC. R905.9.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 19- SHEET 7: SPECIFY HOW MUCH EMBEDMENT IS REQUIRED FOR
 J BOLTS AT BOTTOM PLATE OF STEEL COLUMN AND FOR ANCHOR
 BOLTS AT 3X8 LEDGERIN SECTION 1/7.SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 20- SHEET 8: SPECIFY HEADROOM CLEARANCE IN SECTION 1/8
 TO VERIFY COMPLIANCE WITH SEC. R311.5.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
 ***NOTE: SEE THIS CODE SECTIONTO CHECK HOW DIMENSION
 SHALL BE MEASURED.
  
 21- SHEET 10:
 A) REVISE DESIGN DATA NOTE #2. SEE SEC. R606.4 FOR
 MINIMUM COMPRESSIVE STRESS REQUIRED FOR CONCRETE
 BLOCK.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712