| Plan Review Notes For Permit 07100244 |
| Permit Number |
07100244 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-22 09:03:02 | DENIED | | | REFERENCE: | | | ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. | | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | | REQUIREMENTS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE (FAC). | | | ** FLORIDA STATUTES (FS). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | NOTE: NOT ALL CORRESPONDING LENGTHS ARE INDICATED FOR | | | THE INDICATED CUT SECTIONS OF PIPE, PLEASE INDICATE | | | THESE ON THE RESUBMITTAL. THE EXISTING 1/2" GALV. IS | | | APPROVED UP TO A LONGEST LENGTH OF 70 FEET. IF THE | | | LONGEST LENGTH IS OVER 70 FEET THE SYSTEM WILL NEED TO | | | BE UPGRADED. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|