Plan Review Notes
Plan Review Notes For Permit 07100224
Permit Number 07100224
Review Stop B
Sequence Number 1
Notes
Date Text
2007-10-11 12:35:21BUILDING PLAN REVIEW
 PERMIT: 07100224
 ADD: 1301 SUMMIT BLVD
 CONT: JUPITER ROOFING
 TEL: (561)248-8612
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)THE MASTER PERMIT INDICATES THE FINISHED ROOFING
 WILL BE CORRAGATED METAL, NO PRODUCT APPROVALS WERE
 SUBMITTED FOR THE CORRAGATED ROOFING SYSTEM.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 2) THETAMKO PRODUCT APPROVALS SUBMITTED IN EACH SET
 OF DOCUMENTS HAVE DIFFERENT SYSTEMS CIRCLED, ONE HAS
 SHEET 16 CIRCLED WHILE THE OTHER HAS SHEET 18 CIRCLED,
 PLEASE CORRECT AND SUBMITT ONLY ONE SUB-SYSTEM. NOTE
 SHEET 18 THE MAXIMUM DESIGM PRESSURE REFERENCES THE
 TILE MANUFACTURER'S NOA FOR THE MAXIMUM DESIGN
 PRESSURE.
  
 3) THE OTHER SYSTEM THAT IS CIRCLED ON SHEET 16 IN THE
 SECOND PACKET HAS TWO OPTIONS BOTH OPTIONS WILL END UP
 WITH LOW PRESSURES IN ZONES 2 & 3 PROVIDE THE
 RAS 117 CALCULATIONSFOR ENHANCED FASTENING.
  
 4)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  