| Plan Review Notes For Permit 07100220 |
| Permit Number |
07100220 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-24 15:17:24 | DENIED; | | | NOT ENOUGH INFORMATION TO DO A PLUMBING PLAN REVIEW. ON | | | PERMIT APPLICATION ( DESCRIPTION SECTION)" REPLACE | | | C.I AND COPPER WITH PVC". | | | THE FOLLOWING IS REQUIRED ON THE PLANS. | | | A) A SANITARY RISER DIAGRAM SHOWING ALL PIPE | | | SIZES FOR DRAINAGE AND VENTS. | | | B) REPLACEMENT OF WATER PIPE, COPPER OR CPVC | | | CAN BE USED, NOT PVC FBC PLUMBING SECTION 605.3. | | | IS THE HOUSE AND THE APARTMENT ON ONE WATER | | | METER? IF SO A BACKFLOE PREVENTOR IS REQUIRED AT THE | | | METER. PLEASE SHOW ON PLANS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|