Plan Review Notes
Plan Review Notes For Permit 07100215
Permit Number 07100215
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-24 12:15:22 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE RISER DIAGRAM WOULD INDICATE THE GENERATOR
 BACKFEEDING THE ENTIRE ELECTRICAL SYSTEM WITH 3#4 AND
 1#10 AS DRAWN. PROVIDE A PANEL SCHEDULE FOR THE
 GENERATOR PANEL. 106.3.5.4 FBC AS AMENDED.
  
 2} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 3} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR INDICATING RECOMMENDED SETBACKS FROM
 STRUCTURES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  