| Plan Review Notes For Permit 07100208 |
| Permit Number |
07100208 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-11-06 10:28:38 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE | | | WITH THE ANCHOR SCHEDULE; IN THIS CASE, C1 THROUGH C5. | | | | | | | | | 2.ANCHOR TYPE IS TO BE SPECIFIC.THE 12" SPACING ON | | | THE INSTALLATION SCHEDULE IS NOT COMPLIANT FOR ANY OF | | | THE CONNECTION TYPES FOR ITW TAPCON, AND NOT COMPLIANT | | | FOR SOME CONNECTION TYPES FOR THE OTHER TAPCONS.SEE | | | SHEET 8. | | | | | | 3.PLEASE NOTE THAT SUBSTRATE ON THE INSTALLATION | | | SCHEDULE IS TO BE SUBSTRATE OF THE OPENING, TOP AND | | | BOTTOM, NOT CONSTRUCTION OF THE BUILDING. |
|