Plan Review Notes
Plan Review Notes For Permit 07100207
Permit Number 07100207
Review Stop B
Sequence Number 1
Notes
Date Text
2007-10-29 11:17:28****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)CERTIFICATE OF AUTHORIZATION REQUIRED TO PRACTICE
 ARCHITECTURE THROUGH A COMPANY, FS481.219(2).A SET
 HAS BEEN RETAINED.
  
 2.)ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS
 REQUIRED TO BE ON EACH SHEET (ENGINEER).
  
 3.)THE TOP OF RAIL IS SHOWN AS DISCONTINUOUS, BUT
 HANDRAIL AND GUARDRAIL ARE SHOWN AT 3'6".CLARIFY.
  
 4.)HANDRAIL CANNOT BE DISCONTINUOUS AS SHOWN;
 EXTENSIONS REQUIRED FBC1009.11.4.
  
 5.)DECLARE OCCUPANCY FBC CHAPTER 3.COMPLIANCE WITH
 FBC1009.11.1 IS TO BE SHOWN ON THE PLAN.
  
 6.)ON THE STAIR PLAN, SHOW REQUIRED HANDRAIL
 EXTENSIONS AT THE TOP AND BOTTOM OF THE STAIRS,
 FBC1009.11.5.
  
 7.)SHOW EXTENSIONS ON THE PLAN AND PROVIDE AN
 ELEVATION FOR EITHER THE W OR E SIDE, FBC1009.11.5.
  
 8.)THE SITE PLAN IS NOT CONSISTENT WITH THE PLAN.
 THE PLAN SHOWS AN L SHAPED STAIR, SITE PLAN SHOWS A
 STRAIGHT RUN WITH A LANDING.
  
 9.)DECLARE GOVERNING CODE.
  
 10.)DECLARE WIND DESIGN CRITERIA FBC1603.1.4.
  
  
  