| 2007-11-14 08:41:30 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS |
| | TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | GAS PLAN REVIEW: |
| | DENIED 2ND TIME: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. OK,PREVIOUS COMMENT ADDRESSED. |
| | |
| | 2. NO, PRIVIOUS COMMENT NOT ADDRESSED. |
| | **SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | **NOTE: CORRESPONDING LENGTHS ARE NOT INDICATED ON ALL |
| | CUT SECTIONS OF PIPE. |
| | |
| | 3. OK, PREVIOUS COMMENT ADDRESSED. |
| | |
| | 4. OK, PREVIOUS COMMENT ADDRESSED. |
| | |
| | 5. NO, PREVIOUS COMMENT NOT ADDRESSED. |
| | **BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | **NOTE: THIS INCLUDES THE EXISTING BTU LOAD AS WELL AS |
| | THE PROPOSED BTU LOAD OF GENERATOR. PLEASE REFERENCE |
| | THE PERMIT INFORMATION ATTACHED TO THE GAS COMMENTS |
| | INDICATING EXISTING GAS TO SAID RESIDENCE. |
| | |
| | 6. NO, PREVIOUS COMMENTS NOT ADDRESSED. |
| | **SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | **NOTE: THIS INCLUDES THE EXISTING GAS SYSTEMS LONGEST |
| | LENGTH. AS STATED IN COMMENT #5, PLEASE REFERENCE THE |
| | PERMIT INFORMATION ATTACHED TO THE GAS COMMENTS |
| | INDICATING EXISTING GAS TO SAID RESIDENCE. |
| | |
| | 7. OK, PREVIOUS COMMENT ADDRESSED. |
| | |
| | 8. NO, PREVIOUS COMMENT NOT ADDRESSED. |
| | **SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | **NOTE: THE RESUBMITTED GAS DRAWINGS IS INDICATING THE |
| | GAS DELIVERY PRESSURE AS 2 PSI. PLEASE SUBMIT TWO |
| | COPIES OF MANUFACTURER'S SPECIFICATION SHEETS OF THE MP |
| | REGULATOR INDICATING THE MAKE, MODEL NUMBER, BTU LOAD |
| | CAPACITY, AND A LISTING FROM A NATIONALLY RECOGNIZED |
| | TESTING LABORATORY. |
| | |
| | 9. OK, N/A. |
| | |
| | 10. OK, N/A. |
| | |
| | 11. OK, PREVIOUS COMMENT ADDRESSED. |
| | |
| | **THE FOLLOWING ARE NEW COMMENTS: |
| | |
| | 12. A SHUT OFF VALVE IS REQUIRED BEFORE THE MP |
| | REGULATOR.A} PER FBC-2004 FUEL GAS, SECTION 409.4 MP |
| | REGULATOR VALVES: A LISTED SHUTOFF VALVE SHALL BE |
| | INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR. |
| | |
| | END OF COMMENTS: |
| | |