2007-11-14 08:41:30PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED 2ND TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. OK,PREVIOUS COMMENT ADDRESSED.
  
 2. NO, PRIVIOUS COMMENT NOT ADDRESSED.
 **SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 **NOTE: CORRESPONDING LENGTHS ARE NOT INDICATED ON ALL
 CUT SECTIONS OF PIPE.
  
 3. OK, PREVIOUS COMMENT ADDRESSED.
  
 4. OK, PREVIOUS COMMENT ADDRESSED.
  
 5. NO, PREVIOUS COMMENT NOT ADDRESSED.
 **BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 **NOTE: THIS INCLUDES THE EXISTING BTU LOAD AS WELL AS
 THE PROPOSED BTU LOAD OF GENERATOR. PLEASE REFERENCE
 THE PERMIT INFORMATION ATTACHED TO THE GAS COMMENTS
 INDICATING EXISTING GAS TO SAID RESIDENCE.
  
 6. NO, PREVIOUS COMMENTS NOT ADDRESSED.
 **SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **NOTE: THIS INCLUDES THE EXISTING GAS SYSTEMS LONGEST
 LENGTH. AS STATED IN COMMENT #5, PLEASE REFERENCE THE
 PERMIT INFORMATION ATTACHED TO THE GAS COMMENTS
 INDICATING EXISTING GAS TO SAID RESIDENCE.
  
 7. OK, PREVIOUS COMMENT ADDRESSED.
  
 8. NO, PREVIOUS COMMENT NOT ADDRESSED.
 **SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **NOTE: THE RESUBMITTED GAS DRAWINGS IS INDICATING THE
 GAS DELIVERY PRESSURE AS 2 PSI. PLEASE SUBMIT TWO
 COPIES OF MANUFACTURER'S SPECIFICATION SHEETS OF THE MP
 REGULATOR INDICATING THE MAKE, MODEL NUMBER, BTU LOAD
 CAPACITY, AND A LISTING FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY.
  
 9. OK, N/A.
  
 10. OK, N/A.
  
 11. OK, PREVIOUS COMMENT ADDRESSED.
  
 **THE FOLLOWING ARE NEW COMMENTS:
  
 12. A SHUT OFF VALVE IS REQUIRED BEFORE THE MP
 REGULATOR.A} PER FBC-2004 FUEL GAS, SECTION 409.4 MP
 REGULATOR VALVES: A LISTED SHUTOFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]