2007-11-08 15:37:36 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 COMMENTS FROM PREVIOUS REVIEW:
  
 1} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO
 BE SERVED. 215.5. 702.5, 2005NEC ANDPROVIDE A PANEL
 SCHEDULE FOR THE GENERATOR PANEL. 106.3.5.4 FBC AS
 AMENDED. LOAD CALCULATIONS AND PANEL SCHEDULES WERE
 SUBMITTED FOR TWO PANELS, CLARIFY THE PANEL THE
 GENERATOR WILL FEED. SEE SCHEDULES AND RISER DIAGRAM. *
 THE GENERATOR SPECS HAVE THE OUTPUT AT 75 AMPS. BOTH
 PANEL SCHEDULES/ LOAD CALCS, ARE HIGHER AMPERAGE THAN
 TH OUTPUT OF THE GENSET. IT IS THE DETERMINATION OF
 THIS OFFICE THAT LOADS BEING TRANSFERRED AUTOMATICALLY
 ARE THE LOADS SELECTED UNDER ARTICLE 702.5. UTILITY
 POWER CAN BE DISRUPTED AT ANY TIME, POSSIBLY IN THE
 OWNERS ABSENCE. THEREFORE ALL CONNECTED LOADS WILL BE
 ENERGIZED AS THERE IS NO ONE TO "SELECT" WHICH CIRCUITS
 WILL BE ENERGIZED. HOW ARE LOADS BEING SHED. THERE ARE
 STILL NO GENERATOR PANELS SUBMITTED AIS SHOWN ON THE
 RISER DIAGRAM
  
 2} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.* ONLY THE
 GENERATOR IS ON THE SITE PLAN.
  
 3} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR INDICATING RECOMMENDED SETBACKS FROM
 STRUCTURES
 * COULD NOT FIND THE SETBACK RECOMMENDATIONS IN THE
 DOCUMENTS SUBMITTED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718