| 2007-10-24 11:56:52 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO | | | BE SERVED. 215.5. 702.5, 2005NEC ANDPROVIDE A PANEL | | | SCHEDULE FOR THE GENERATOR PANEL. 106.3.5.4 FBC AS | | | AMENDED. LOAD CALCULATIONS AND PANEL SCHEDULES WERE | | | SUBMITTED FOR TWO PANELS, CLARIFY THE PANEL THE | | | GENERATOR WILL FEED. SEE SCHEDULES AND RISER DIAGRAM. | | | | | | 2} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON | | | A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE, | | | DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH | | | ARTICLES 225 AND 230 CAN BE REVIEWED. | | | | | | 3} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE | | | GENERATOR INDICATING RECOMMENDED SETBACKS FROM | | | STRUCTURES. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|