Plan Review Notes
Plan Review Notes For Permit 07100203
Permit Number 07100203
Review Stop B
Sequence Number 2
Notes
Date Text
2007-10-18 16:12:52****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)TWO DIFFERENT FASTENING PATTERNS WERE SUBMITTED.
 THE SUPPLEMENTAL INFORMATION SECTION D SPECIFIES 2"
 SPACING.FASTENERS ARE TO BE A MINIMUM OF 4" PER
 RAS117.
  
 2.)THE SECTION C (LOW SLOPED ROOF SYSTEM) SPECIFIES
 FIELD FASTENING WHICH CONFLICTS WITH THE NOA.SUBMIT
 ONLY ONE ENHANCED FASTENING PATTERN, TWO SETS.CONFIRM
 COMPLIANCE AND USE THE FIELD FASTENING PATTERN FROM THE
 NOA.
  