| Date |
Text |
| 2007-10-17 15:49:57 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| | ** FLORIDA STATUTES (FS). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. NOTE: SHEET 1, OF THE SUBMITTED PLANS HAVE AN |
| | ARCHITECTURAL TITLE BLOCK FROM EVERETT H JENNER |
| | AR-0007573, PER FAC-CODE-61G1-16001 ARCHITECT'S AND |
| | INTERIOR DESIGNER'S SEAL: |
| | EACH ARCHITECT AND INTERIOR DESIGNER |
| | SHALL ACQUIRE A SEAL WITH WHICH HE OR |
| | SHE SHALL IDENTIFY ALL PLANS, |
| | SPECIFICATIONS OR REPORTS PREPARED OR |
| | ISSUED BY HIM OR HER AND FILED FOR |
| | PUBLIC RECORD. THE SEAL SHALL BE OF A |
| | TYPE WHICH WILL MAKE AN IMPRESSION ON |
| | THE SURFACE OF PRINTS OR OTHER |
| | DUPLICATIONS OF DRAWINGS, AND AS |
| | APPROPRIATE, UPON SPECIFICATION PAGES, |
| | AND OTHER ARTICLES OF SERVICE. |
| | |
| | 2. PER FBC-2004 CHAPTER 1, SECTION 106.1.2 PLEASE |
| | SUBMIT ADDITIONAL DATA PER THE FOLLOWING FBC-2004 W/ |
| | 06, REV. PLUMBING, CODE SECTIONS, 601.1 WATER SUPPLY |
| | DESIGN (IRRIGATION), 608, POTABLE WATER PTOTECTION, AND |
| | 305.3 STRESS AND STRAIN. |
| | |
| | A} 601.1 & 608: CLEARLY INDICATE THE BACKFLOW |
| | PREVENTER LOCATION ON THE RESUBMITTED PLANS AND PROVIDE |
| | A SYMBOL FOR IT IN THE IRRIGATION LEGEND. |
| | |
| | B} 601.1 & 608: CLEARLY INDICATE IF THE BACKFLOW |
| | PREVENTER IS EXISTING OR NEW ON THE RESUBMITTED PLANS. |
| | |
| | |
| | C} 305.3: CLEARLY INDICATE ON THE RESUBMITTED PLAN ALL |
| | REQUIRED SLEEVE LOCATIONS FOR THE IRRIGATION PIPING IN |
| | PARKING LOTS, AND SIDEWALK AREAS. |
| | |
| | END OF COMMENTS: |
| | |