| 2007-10-16 10:12:50 | **** DENIED **** |
| | |
| | |
| | 1) NOTE:PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT |
| | CODES ARE STATED ON PLANS. |
| | PLEASE KNOW THAT ALL PERMIT APPLICATIONS DATED AFTER |
| | DECEMBER 8TH, 2006 FALL UNDER THE FOLLOWING CODES AT A |
| | MINIMUM. |
| | PLEASE BE AWARE OF ANY OTHER CODES WHICH MAY BE |
| | REFERENCED BY OTHER TRADES DURING THEIR REVIEW. THE |
| | FOLLOWING IS NEEDED ON ELECTRICAL SHEETS AS WELL AS |
| | FIRE ALARM SHEETS BY THIS REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | |
| | ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES FOR |
| | CODES. |
| | |
| | 2) NOTE: PLEASE SUBMIT PLANS WHICH ARE NOT DONE IN |
| | PEN/PENCIL. PLEASE SEE MINIMUM CONSTRUCTION DOCUMENTS |
| | STANDARDS PER FBC 106.1 |
| | |
| | 3) NOTE: PLEASE SUBMIT ELECTRICAL WITH MORE DETAIL FOR |
| | NEW ELEVATOR. THIS NEEDS TO INCLUDE SIZE OF MOTOR, |
| | LOADS, ETC. |
| | THE OVER CURRENT PROTECTION WHICH IS SHOWN AS EXISTING |
| | ALONG WITH CONDUCTOR SIZES CAN NOT BE VERIFIED FOR |
| | MOTOR AT THIS TIME. |
| | PLEASE SEE THAT STATING SOME OF THE CODES IN LIEU OF |
| | SPECIFIC DETAIL CAN NOT BE ACCEPTED. |
| | PLEASE SEE THERE ARE SEVERAL SECTIONS OF NEC 620 WHICH |
| | INFORMATION IS NEEDED. DISCONNECT LOCATIONS FOR BRANCH |
| | CIRCUITS; MOTORS ETC ARE REQUIRED TO BE GROUPED IN ONE |
| | LOCATION. |
| | PLEASE SEE PLANS ARE MISSING AN EQUIPMENT ROOM, PIT, |
| | AND OTHER ITEMS WHICH ARE NOT CLEAR IF THESE WILL BE |
| | REQUIRED. |
| | THERE IS A STRUCTURAL SHEET WHICH DOES SHOW A LAYOUT |
| | FOR EQUIPMENT HOWEVER THIS DOES NOT CORRELATE WITH |
| | ELECTRICAL PLANS. |
| | PLEASE SEE THE ELECTRICAL DETAILS ON SHEETS DO NOT |
| | CORRELATE WITH THE ELECTRICAL DONE BY THE ELECTRICAL |
| | CONTRACTOR. THIS SHOWS 3-POLE BREAKERS AND ELECTRICAL |
| | BY CONTRACTOR SHOWS 2-POLE BREAKERS. |
| | PLEASE SUBMIT COMPLETE ELECTRICAL PLANS SHOWING LAYOUT |
| | OF ALL EQUIPMENT. PLEASE INCLUDE ALL DETAILS. |
| | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION. |
| | NEC 430, 620, 310.16, 240.4 ETC |
| | |
| | 4) NOTE: PLEASE SEE SHEET WHICH CONTAINS THE ELECTRICAL |
| | EQUIPMENT LAYOUT DOES NOT CONTAIN ANY TITLE BLOCK ALONG |
| | WITH OTHER SHEETS WHICH ARE SIGNED, DATED AND SEALED BY |
| | THE ENGINEER. |
| | FAC 61G15-23.002 |
| | |
| | 5) NOTE: PLEASE VERIFY WITH THE STATE ANY POSSIBLE |
| | REQUIREMENTS FOR A/C TO BE PLACED IN THE EQUIPMENT |
| | ROOM. THIS HAS COME TO OUR ATTENTION THAT THIS IS BEING |
| | REQUIRED AT SEVERAL LOCATIONS. |
| | THIS IS NOTED FOR INFORMATION ONLY. |
| | |
| | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET |
| | COMPLETED ON PLANS FOR REVIEW, NOT ALL COMMENTS MAY BE |
| | PRESENT AT THIS TIME. |
| | |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL |
| | AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |