| Date |
Text |
| 2007-12-06 10:05:53 | ** DENIED 3RD REVIEW ** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM TWO PREVIOUS REVIEWS ARE |
| | STILL IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS DUE |
| | TO CHANGES MADE TO PLANS. |
| | |
| | 1) NOTE: PLEASE SEE THE RESPONSE LETTER PROVIDED BY THE |
| | DESIGN PROFESSIONAL ONLY RESPONDS PART OF THE NOTES |
| | FROM THE 2ND REVIEW. THE NOTE #1 FROM PREVIOUS REVIEW |
| | #2 SPECIFICALLY MENTIONED THAT ALL NOTES FROM FIRST |
| | REVIEW REMAINED WITH THE EXCEPTION OF NOTE #2. PLEASE |
| | KNOW A RESPONSE LETTER IS NOT REQUIRED ALTHOUGH IS |
| | HELPFUL IN THE REVIEW PROCESS IF COMPLETE. |
| | |
| | 2) NOTE: PLEASE SEE NOTE #1 FROM ORIGINAL REVIEW WHICH |
| | STILL NEEDS ADDRESSING. |
| | PLEASE LIST ALL RELEVANT CODES ON PLANS. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 (WHERE APPLICABLE) AS FIRE ALARM SYSTEM |
| | HAS NOT BEEN DETERMINED, THIS CODE WILL REMAIN. |
| | |
| | 2) NOTE: PLEASE SEE PANEL SCHEDULE STILL LIST #8 FOR |
| | 90AMP OVER CURRENT PROTECTION FOR THE RTU. THIS EXCEEDS |
| | 310.16 FOR RATING OF CONDUCTORS. |
| | PLEASE ALSO SEE THE PANEL LIST THIS AS A 2-POLE WHERE |
| | SPACES IN PANEL AND CONDUCTORS LEND TO THIS A 3-PHASE? |
| | 240.4, 310.16 ETC |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 3) NOTE: PLEASE SEE THE RISER IS MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS AFTER ALL FIRST MEANS OF |
| | DISCONNECTS. |
| | 250.110, 250.24, 250.122 |
| | |
| | 4) NOTE: PLEASE SEE NOTES UNDER PERMIT APPLICATION FOR |
| | OTHER SCOPE OF WORK AT THIS SAME LOCATION AS THE |
| | SERVICE RISER AS SHOWN CONTAINS SEVERAL NON-CODE |
| | COMPLIANT ITEMS. |
| | PLEASE GO OVER THE NEC 2005 AS THE SERVICE WILL BE |
| | REQUIRED TO MEET THE CURRENT CODE. |
| | THERE ARE ITEMS ON RISER UNDER THIS REVIEW AND THE |
| | REVIEW OF THE OTHER APPLIED PERMIT FOR THIS LOCATION |
| | WHICH NEVER MET THE MINIMUM CODE AS SHOWN. |
| | PLEASE GIVE MORE DETAILS FOR COMPLETE RISER SHOWING NEW |
| | AND EXISTING AND ADJUST FOR CODE COMPLIANCE. PLEASE SEE |
| | SOME EXAMPLES ARE NOTED BELOW: |
| | PLEASE SEE MISSING EQUIPMENT GROUNDS AS NOTED ABOVE. |
| | PLEASE SEE THE GROUNDING ELECTRODE CONDUCTOR IS NOT |
| | LARGE ENOUGH PER 250.66. |
| | PLEASE SEE 40AMP DISCONNECT STILL SHOWN WITH 5-#8 |
| | CONDUCTORS TO A 2-POLE 40AMPS DISCONNECT IN A 3/4 INCH |
| | CONDUIT. |
| | PLEASE SEE NO MAIN FOR TAPPED CONDUCTORS FOR NEW PANEL |
| | PER 240.21, 310.16, 240.4, 408.36 ETC |
| | PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY AND EXIT |
| | LIGHTS (THIS WILL BE NOTED BELOW FOR SPACE). PLEASE SEE |
| | NO PANEL SCHEDULE WAS SUBMITTED FOR HPB, YET THIS PANEL |
| | IS IN THE NEW TENANT SPACE BEING CREATED. 408.4, 240.4, |
| | 310.16 ETC. |
| | FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 5) NOTE: PLEASE SEE FBC 13-101.1, 13-415.1.ABC.1.1, |
| | .1.2AS NO LIGHTING CONTROLS OR SYSTEM WAS SUBMITTED |
| | FOR REVIEW. LIGHTING IS NOTED AS *ALL EXISTING* WITH |
| | NEW CIRCUITS YET NO LIGHTING CONTROLS WERE SUBMITTED. |
| | |
| | 6) NOTE: PLEASE SEE CIRCUITING PER 700.12F FOR |
| | EMERGENCY AND EXIT LIGHTS SHALL BE CIRCUITED TO THE |
| | LOCAL BRANCH CIRCUIT FEEDING LOCAL LIGHTING. |
| | |
| | 7) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES PER |
| | 210.62, 220.43 |
| | THE NEW SIGN CIRCUIT WHICH IS PART OF 600.5 IS NOT THE |
| | SAME. |
| | |
| | 8) NOTE: PLEASE SEE TWO SETS OF ENERGY CALCULATIONS |
| | WERE SUBMITTED SHOWING A METHOD *A* AND METHOD *B*. |
| | PLEASE SEE THAT METHOD *A* CAN NOT BE USED AS THIS IS |
| | NOT A *WHOLE BUILDING*. |
| | PLEASE SEE 13-415.2 AS THIS IS ALREADY A CONDITIONED |
| | SPACE AND RE-FEEDING THE EXISTING UNIT. |
| | PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED DO NOT |
| | CONTAIN ANY INPUT DATA REPORTS AS REQUIRED. PLEASE SEE |
| | PAGE #2 WHICH SPECIFICALLY MENTIONS THAT THE |
| | CALCULATION SUMMARY SHEETS MUST BE ACCOMPANIED BY THE |
| | INPUT DATA REPORT. |
| | PLEASE SEE THE JURISTICTION IS LISTED AS PALM BEACH |
| | COUNTY. |
| | WE ARE UNABLE TO REVIEW FOR CODE COMPLIANCE AT THIS |
| | TIME. |
| | PLEASE BE SURE TO COMPLETE FIXTURE LEGEND FOR |
| | FIXTURES. |
| | |
| | 9) NOTE: PLEASE PROVIDE NEW ROOF-TOP GFI PER 210.63, |
| | 210.8. |
| | AS THIS IS A NEW TENANT, ANY EXISTING DEVICES WOULD |
| | NOT BE FED FROM OTHER POWER SOURCE LOCATIONS. |
| | |
| | 10) NOTE: PLEASE VERIFY PANEL AS SHOWN AS 200AMPS IS |
| | 200AMPS. THIS IS MOST LIKELY A 225AMP AND WILL CONTAIN |
| | A 200AMP MCB. |
| | PANEL MENTIONS *FUSED AT DISCONNECT* HOWEVER AS NO |
| | DISCONNECT IS SHOWN ON RISER THIS IS NOT POSSIBLE. |
| | PLEASE VERIFY AND ADJUST AS NOTED ABOVE FOR TAPPED |
| | CONDUCTORS. |
| | 240.21, 310.16, 90.7, 110.3 ETC |
| | FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 11) NOTE: PLEASE SEE NO RESPONSE WAS PROVIDED ON |
| | WHETHER OR NOT THE BUILDING CONTAINS A FIRE ALARM |
| | SYSTEM? |
| | PLEASE SEE THE MECHANICAL PLANS INDICATE A NEW HORN |
| | STROBE FOR UNIT AND AS THIS IS NOT SHOWN ON ELECTRICAL |
| | IT IS BEING *ASSUMED* THIS IS LOCATED IN SPACE. PLEASE |
| | KNOW IF ANY FA SYSTEM IS LOCATED OR WILL BE MODIFIED, |
| | ALL DEVICES SHALL COMPLY WITH FBC 11-4.28.1,.2 AND |
| | .3(4). |
| | |
| | 12) NOTE: PLEASE SEE WALL WHICH CONTAINS RECEPTACLES |
| | WHICH MENTIONS TO PROVIDE EXTENSIONS, HOWEVER NO |
| | CIRCUITING ON HOW THESE ARE FED IS SHOWN. |
| | PLEASE ALSO COORDINATE SHEET M-1, E-2 AS THE ELECTRICAL |
| | SHEETS E-1 ONLY CONTAINS TWO ELECTRICAL PANELS AND E-2 |
| | CONTAINS 3. |
| | FBC 106.1.2, ADDITIONAL INFORMATION/COORDINATION. |
| | |
| | 13) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | |
| | ** PLEASE KNOW THAT A FIELD INSPECTION MAY BE NEEDED TO |
| | GO OVER EXISTING WORK AND PROPOSED NEW. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |